NOTICE
The LED flash patterns of the VLT® FCD 300 PROFIBUS Converter MCA 117 are not compatible with the patterns of the FCD
300/FCM 300 PROFIBUS LEDs.
4.6 Factory Settings
The VLT® FCD 300 PROFIBUS Converter MCA 117 is delivered from factory with the optimal settings to replace a VLT® Decentral Drive
FCD 300. If the VLT® FCD 300 PROFIBUS Converter MCA 117 is moved from one application to another, it is recommend to initialize the
drive. This initialization activates the factory settings and re-invoke of the Ident number detection. If the drive has been delivered from
factory with the option installed, initialization can be skipped.
Do the initialization via:
•
Parameter 14-22 Operation Mode
, or
•
Three-finger reset by removing power to the drive, pressing [Status], [Main Menu], and [OK], and applying 400 V AC or 24 V DC
back-up power to the drive.
The MCA 117 sets the parameters of the FCD 302 so that the FCD 302/MCA 117 emulate the FCD 300 in the best way.
The parameters of the VLT® Decentral Drive FCD 302 are set to factory values and some FCD 302 parameters are set to values that
match the initial values of VLT® Decentral Drive FCD 300.
Factory copy via the FCD 300
parameter 006 Setup Copy
is supported and initializes the FCD 302 and sets it to the FCD 300 default
settings.
Table 7: Parameters Set During Initialization
Parameter
Initialization setting
Parameter 0-02 Motor Speed Unit
[Hz]
Parameter 1-51 Min Speed Normal Magnetizing [RPM]
30 RPM
Parameter 1-52 Min Speed Normal magnetising [Hz]
1.0 Hz
Parameter 1-64 Resonance Damping
0
Paramter 1-81 Min Speed for Function at Stop [RPM]
3 RPM
Parameter 1-82 Min Speed for Function at Stop [Hz]
0.1 Hz
Parameter 1-93 Thermistor Resource
Analog input 54
Parameter 2-10 Brake Function
[0] Off
Parameter 2-17 Overvoltage Control
[0] Off
Parameter 3-00 Reference Range
min – max
Parameter 3-01 Reference/Feedback Unit
[1]%
Parameter 3-03 Maximum Reference
50.000
Parameter 3-11 Jog Speed [Hz]
10.0 Hz
Parameter 3-16 Reference Resource 2
[0] No function
Parameter 3-19 Jog Speed [RPM]
300 RPM
Parameter 4-13 Motor Speed High Limit [RPM]
3960 RPM
Configuring the System
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
AQ289550754901en-000101 / 130R0890
22 | Danfoss A/S © 2019.11