0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 - 255 ] View a list of all the set-ups linked by means of
. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
setups are linked to that parameter setup.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Prog. Set-ups / Channel
Range:
Function:
0
*
[-2147483648
- 2147483647 ]
View the setting of
for each of the four different
communication channels. When the
number is displayed in hex, as it is in the
LCP, each number represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1.5.
Example: The number AAAAAA21h means
that the FC-bus selected Set-up 2 in
, the LCP selected
Set-up 1 and all others used the active set-
up.
3.2.3 0-2* LCP Display
Define the variables displayed in the Graphical Local
Control Panel.
NOTE
Please refer to
,
and
for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in line
1, left position.
[0]
*
None
No display value selected
0-20 Display Line 1.1 Small
Option:
Function:
[37]
Display Text 1
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[38]
Display Text 2
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[39]
Display Text 3
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[89]
Date and Time
Readout
Displays the current date and time.
[953]
Profibus Warning
Word
Displays Profibus communication
warnings.
[1005]
Readout Transmit
Error Counter
View the number of CAN control
transmission errors since the last
power-up.
[1006]
Readout Receive
Error Counter
View the number of CAN control
receipt errors since the last power-
up.
[1007]
Readout Bus Off
Counter
View the number of Bus Off events
since the last power-up.
[1013]
Warning
Parameter
View a DeviceNet-specific warning
word. One separate bit is assigned
to every warning.
[1115]
LON Warning
Word
Shows the LON-specific warnings.
[1117]
XIF Revision
Shows the version of the external
interface file of the Neuron C chip
on the LON option.
[1118]
LonWorks
Revision
Shows the software version of the
application program of the Neuron
C chip on the LON option.
[1230]
Warning
Parameter
[1501]
Running Hours
View the number of running hours
of the motor.
[1502]
kWh Counter
View the mains power consumption
in kWh.
[1600]
Control Word
View the Control Word sent from
the frequency converter via the
serial communication port in hex
code.
[1601]
Reference [Unit]
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in selected unit.
[1602]
*
Reference [%]
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in percent.
[1603]
Status Word
Present status word
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
27