0-20 Display Line 1.1 Small
Option:
Function:
[1605]
Main Actual Value
[%]
View the two-byte word sent with
the Status word to the bus Master
reporting the Main Actual Value.
[1609]
Custom Readout
View the user-defined readouts as
defined in
and
[1610]
Power [kW]
Actual power consumed by the
motor in kW.
[1611]
Power [hp]
Actual power consumed by the
motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Frequency
Motor frequency, i.e. the output
frequency from the frequency
converter in Hz.
[1614]
Motor Current
Phase current of the motor
measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
[1616]
Torque [Nm]
Present motor load as a percentage
of the rated motor torque.
[1617]
Speed [RPM]
Motor speed reference. Actual
speed will depend on slip compen-
sation being used (compensation
set in
). If not
used, actual speed will be the value
read in the display minus motor
slip.
[1618]
Motor Thermal
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced,
in percentage.
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link Voltage
Intermediate circuit voltage in the
frequency converter.
[1632]
Brake Energy /s
Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
[1633]
Brake Energy /2
min
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 seconds.
0-20 Display Line 1.1 Small
Option:
Function:
[1634]
Heatsink Temp.
Present heat sink temperature of
the frequency converter. The cut-
out limit is 95 ± 5
°
C; cutting back
in occurs at 70 ± 5
°
C.
[1635]
Inverter Thermal
Percentage load of the inverters
[1636]
Inv. Nom. Current Nominal current of the frequency
converter
[1637]
Inv. Max. Current
Maximum current of the frequency
converter
[1638]
SL Controller
State
State of the event executed by the
control
[1639]
Control Card
Temp.
Temperature of the control card.
[1643]
Timed Actions
Status
See parameter group
23-0* Timed
Actions
.
[1650]
External Reference Sum of the external reference as a
percentage, i.e. the sum of analog/
pulse/bus.
[1652]
Feedback [Unit]
Reference value from programmed
digital input(s).
[1653]
Digi Pot Reference View the contribution of the digital
potentiometer to the actual
reference Feedback.
[1654]
Feedback 1 [Unit]
View the value of Feedback 1. See
also par. 20-0*.
[1655]
Feedback 2 [Unit]
View the value of Feedback 2. See
also par. 20-0*.
[1656]
Feedback 3 [Unit]
View the value of Feedback 3. See
also par. 20-0*.
[1658]
PID Output [%]
Returns the Drive Closed Loop PID
controller output value in percent.
[1660]
Digital Input
Displays the status of the digital
inputs. Signal low = 0; Signal high =
1.
Regarding order, see
. Bit 0 is at the extreme right.
[1661]
Terminal 53
Switch Setting
Setting of input terminal 53. Current
= 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as a
reference or protection value.
[1663]
Terminal 54
Switch Setting
Setting of input terminal 54. Current
= 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as
reference or protection value.
[1665]
Analog Output 42
[mA]
Actual value at output 42 in mA.
Use
to
select the variable to be
represented by output 42.
Parameter Description
VLT
®
HVAC Drive Programming Guide
28
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3
3