20 mA
10 mA
0/4 mA
100%
200%
0%
Max ref
Max ref X 20/10
Min ref
130BA857.10
6-53 Terminal 42 Output Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of Output 42 if
controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Holds the preset level of Output 42.
In case of a bus timeout and a timeout
function is selected in
the output will preset to this
level.
3.8.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as
Option:
Function:
[0]
*
No operation
6-61 Terminal X30/8 Min. Scale
Range:
Function:
0.00
%
*
[0.00 -
200.00 %]
Scales the minimum output of the selected
analog signal on terminal X30/8. Scale the
minimum value as a percentage of the
maximum signal value, i.e. 0mA (or 0hz) is
desired at 25% of the maximum output value
and 25% is programmed. The value can
never be higher than the corresponding
setting in
6-62 Terminal X30/8 Max. Scale
if
value is below 100%.
This parameter is active when option module
MCB 101 is mounted in the frequency
converter.
6-62 Terminal X30/8 Max. Scale
Range:
Function:
100.00
%
*
[0.00
-
200.00
%]
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the desired maximum value of the current
signal output. Scale the output to give a lower
current than 20mA at full scale or 20mA at an
output below 100% of the maximum signal
value. If 20mA is the desired output current at
a value between 0 - 100% of the ful-scale
output, program the percentage value in the
parameter, i.e. 50% = 20mA. If a current
between 4 and 20mA is desired at maximum
output (100%), calculate the percentage value
as follows:
20
mA / desired maximum current × 100 %
i.e. 10 mA : 20 mA
10
mA × 100 % = 200 %
6-63 Terminal X30/8 Output Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Contains the value to apply to the
output terminal, when it is
configured as [Bus Controlled].
6-64 Terminal X30/8 Output Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the value to apply to the
output terminal, when it is configured
as [Bus Controlled Timeout] and time-
out is detected.
Parameter Description