7.10.5. Preset Single Register (06 HEX)
Description
This function presets a value into a single holding register.
Query
The query message specifies the register reference to be preset. Register addresses start at zero,
i.e. register 1 is addressed as 0.
Field Name
Example (HEX)
Slave Address
01
Function
06
Register Address HI
00
Register Address LO
01
Preset Data HI
00
Preset Data LO
03
Error Check (CRC)
-
Response
Response The normal response is an echo of the query, returned after the register contents have
been passed.
Field Name
Example (HEX)
Slave Address
01
Function
06
Register Address HI
00
Register Address LO
01
Preset Data HI
00
Preset Data LO
03
Error Check (CRC)
-
7. RS-485 Installation and Set-up
VLT
®
HVAC Drive Design Guide
144
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
7