3.4.2 2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters.
Only valid for drives with brake chopper.
2-10 Brake Function
Option:
Function:
Available selections depend on
[0] Asynchron:
[0] off
[1] Resistor brake
[2] AS brake
[1] PM non salient:
[0] off
[1] Resistor brake
[0]
*
Off
No brake resistor installed.
[1]
Resistor
brake
Brake resistor incorporated in the system, for
dissipation of surplus brake energy as heat.
Connecting a brake resistor allows a higher DC
link voltage during braking (generating
operation). The Resistor brake function is only
active in frequency converters with an integral
dynamic brake.
[2]
AC brake
AC Brake will only work in Compressor Torque
mode in
.
2-11 Brake Resistor (ohm)
Range:
Function:
Size
related
*
[ 5.00 -
65535.00
Ohm]
Set the brake resistor value in Ohms.
This value is used for monitoring the
power to the brake resistor in
. This
parameter is only active in frequency
converters with an integral dynamic
brake.
Use this parameter for values without
decimals. For a selection with two
decimals, use
30-81 Brake Resistor
(ohm)
.
2-12 Brake Power Limit (kW)
Range:
Function:
Size
related
*
[ 0.001 -
2000.000
kW]
is the expected
average power dissipated in the brake
resistor over a period of 120s. It is used as
the monitoring limit for
16-33 Brake
Energy /2 min
and thereby specifies when a
warning/ alarm is to be given.
To calculate
the following formula can be used.
Pbr,avg W =
Ubr2 V × tbr s
Rbr Ω × Tbr s
2-12 Brake Power Limit (kW)
Range:
Function:
P
br,avg
is the average power dissipated in
the brake resistor, R
br
is the resistance of
the brake resistor. t
br
is the active breaking
time within the 120 s period, T
br
.
U
br
is the DC voltage where the brake
resistor is active. This depends on the unit
as follows:
T2 units: 390V
T4 units: 778V
T5 units: 810V
T6 units: 943V / 1099V for D – F frames
T7 units: 1099V
NOTE
If R
br
is not known or if T
br
is different
from 120s, the practical approach is to
run the brake application, readout
16-33 Brake Energy /2 min
and then
enter this + 20% in
2-12 Brake Power
Limit (kW)
.
2-13 Brake Power Monitoring
Option:
Function:
This parameter is only active in frequency
converters with an integral dynamic brake.
This parameter enables monitoring of the
power to the brake resistor. The power is
calculated on the basis of the resistance
(
, the DC link voltage,
and the resistor duty time.
[0]
*
Off
No brake power monitoring is required.
[1]
Warning
Activates a warning on the display when the
power transmitted over 120 sec. exceeds 100%
of the monitoring limit (
The warning disappears when the transmitted
power falls below 80% of the monitoring limit.
[2]
Trip
Trips the frequency converter and displays an
alarm when the calculated power exceeds
100% of the monitoring limit.
[3]
Warning
and trip
Activates both of the above, including
warning, trip and alarm.
If power monitoring is set to
Off
[0] or
Warning
[1], the
brake function remains active even if the monitoring limit
is exceeded. This may lead to thermal overload of the
resistor. It is also possible to generate a warning via a
relay/digital output. The measuring accuracy of the power
monitoring depends on the accuracy of the resistance of
the resistor (better than
±
20%).