Crusher jaw
Motor Full Load Current
Start mode
Constant current
Start ramp time
10 s
Current limit
450%
Excess start time
40 s
Locked rotor time
30 s
Table 7.10 Suggested Values for Crusher Jaw Applications
7.2.3 Loggings
To view performance information in real-time graphs, enter
the
Loggings
menu.
•
Current (%FLC).
•
Motor Temp (%).
•
Motor kW (%).
•
Motor kVA (%).
•
Motor pf.
The newest information is shown at the right side of the
screen. The graph can be paused to analyze data by
pressing and holding the [OK] key. To restart the graph,
press and hold [OK].
7.3 Main Menu
[Main Menu] provides access to menus for setting up the
soft starter for advanced applications and for monitoring
performance.
7.3.1 Parameters
Parameters allow viewing and changing all programmable
parameters that control how the soft starter operates.
To open
Parameters
, press [Main Menu] then select
Parameters
.
Navigating through parameters
•
To scroll through parameter groups, press [
▲
] or
[
▼
].
•
To view the parameters in a group, press [OK].
•
To return to the previous level, press [Back].
•
To close
Parameters
, press the [Back].
Changing a parameter value
•
Scroll to the appropriate parameter and press
[OK] to enter edit mode.
•
To alter the parameter setting, press [
▲
] and [
▼
].
•
To save changes, press [OK]. The setting shown
on the display is saved and the LCP returns to the
parameter list.
•
To cancel changes, press [Back]. The LCP returns
to the parameter list without saving changes.
7.3.2 Parameter Shortcut
The VLT
®
Soft Starter MCD 500 also includes a parameter
shortcut, which gives direct access to a parameter within
the
Parameters
menu.
•
To access the parameter shortcut, press [Main
Menu] for 3 s.
•
Press [
▲
] or [
▼
] to select the parameter group.
•
Press [OK] or [Back] to move the cursor.
•
Press [
▲
] or [
▼
] to select the parameter number.
Parameter shortcut
Please enter a
parameter number
01-01
Programming
VLT
®
Soft Starter MCD 500
58
Danfoss A/S © 05/2016 All rights reserved.
MG17K602
7