15-30 Alarm Log: Error Code
Array [10]
Range:
Function:
0
*
[0 - 255 ] View the error code and look up its meaning in
the
Troubleshooting
chapter.
15-31 Alarm Log: Value
Array [10]
Range:
Function:
0
*
[-32767 - 32767 ] View an extra description of the error. This
parameter is mostly used in combination
with alarm 38 ‘internal fault’.
15-32 Alarm Log: Time
Array [10]
Range:
Function:
0 s
*
[0 - 2147483647 s] View the time when the logged event
occurred. Time is measured in seconds
from frequency converter start-up.
15-33 Alarm Log: Date and Time
Range:
Function:
Size related
*
[0 - 0 ]
3.15.5 15-4* Drive Identification
Parameters containing read only information about the
hardware and software configuration of the frequency
converter.
15-40 FC Type
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 1-6.
15-41 Power Section
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 7-10.
15-42 Voltage
Range:
Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 11-12.
15-43 Software Version
Range:
Function:
0
*
[0 - 0 ] View the combined SW version (or ‘package version’)
consisting of power SW and control SW.
15-44 Ordered Typecode String
Range:
Function:
0
*
[0 - 0 ] View the type code string used for re-ordering the
frequency converter in its original configuration.
15-45 Actual Typecode String
Range:
Function:
0
*
[0 - 0 ]
View the actual type code string.
15-46 Frequency Converter Ordering No
Range:
Function:
0
*
[0 - 0 ] View the 8-digit ordering number used for re-
ordering the frequency converter in its original
configuration.
15-47 Power Card Ordering No
Range:
Function:
0
*
[0 - 0 ]
View the power card ordering number.
15-48 LCP Id No
Range:
Function:
0
*
[0 - 0 ]
View the LCP ID number.
15-49 SW ID Control Card
Range:
Function:
0
*
[0 - 0 ] View the control card software version number.
15-50 SW ID Power Card
Range:
Function:
0
*
[0 - 0 ] View the power card software version number.
15-51 Frequency Converter Serial Number
Range:
Function:
0
*
[0 - 0 ]
View the frequency converter serial number.
15-53 Power Card Serial Number
Range:
Function:
0
*
[0 - 0 ]
View the power card serial number.
15-59 CSIV Filename
Range:
Function:
Size related
*
[0 - 0 ]
CSIV Filename readout.
3.15.6 15-6* Option Ident.
This read-only parameter group contains information about
the hardware and software configuration of the options
installed in slots A, B, C0 and C1.
15-60 Option Mounted
Range:
Function:
0
*
[0 - 0 ]
View the installed option type.
Parameter Description
VLT
®
HVAC Drive Programming Guide
112
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3