13-51 SL Controller Event
Array [20]
Option:
Function:
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[76]
Digital Input x30 2
[77]
Digital Input x30 3
[78]
Digital Input x30 4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
13-52 SL Controller Action
Array [20]
Option:
Function:
Select the action corresponding to the
SLC event. Actions are executed when
the corresponding event (defined in
) is evaluated as
true. The following actions are available
for selection:
[0]
*
Disabled
[1]
No action
[2]
Select set-up 1
Changes the active set-up (
) to ‘1’.
[3]
Select set-up 2
Changes the active set-up (
) to ‘2’.
[4]
Select set-up 3
Changes the active set-up (
) to ‘3’.
[5]
Select set-up 4
Changes the active set-up (
) to ‘4’. If the set-up is changed, it
will merge with other set-up commands
coming from either the digital inputs or
via a fieldbus.
[10]
Select preset ref 0 Selects preset reference 0.
[11]
Select preset ref 1 Selects preset reference 1.
[12]
Select preset ref 2 Selects preset reference 2.
[13]
Select preset ref 3 Selects preset reference 3.
[14]
Select preset ref 4 Selects preset reference 4.
[15]
Select preset ref 5 Selects preset reference 5.
[16]
Select preset ref 6 Selects preset reference 6.
13-52 SL Controller Action
Array [20]
Option:
Function:
[17]
Select preset ref 7 Selects preset reference 7. If the active
preset reference is changed, it will
merge with other preset reference
commands coming from either the
digital inputs or via a fieldbus.
[18]
Select ramp 1
Selects ramp 1
[19]
Select ramp 2
Selects ramp 2
[22]
Run
Issues a start command to the frequency
converter.
[23]
Run reverse
Issues a start reverse command to the
frequency converter.
[24]
Stop
Issues a stop command to the frequency
converter.
[26]
DC Brake
Issues a DC stop command to the
frequency converter.
[27]
Coast
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28]
Freeze output
Freezes the output frequency of the
frequency converter.
[29]
Start timer 0
Starts timer 0, see
for further description.
[30]
Start timer 1
Starts timer 1, see
for further description.
[31]
Start timer 2
Starts timer 2, see
for further description.
[32]
Set digital out A
low
Any output with ‘digital output 1’
selected is low (off).
[33]
Set digital out B
low
Any output with ‘digital output 2’
selected is low (off).
[34]
Set digital out C
low
Any output with ‘digital output 3’
selected is low (off).
[35]
Set digital out D
low
Any output with ‘digital output 4’
selected is low (off).
[36]
Set digital out E
low
Any output with ‘digital output 5’
selected is low (off).
[37]
Set digital out F
low
Any output with ‘digital output 6’
selected is low (off).
[38]
Set digital out A
high
Any output with ‘digital output 1’
selected is high (closed).
[39]
Set digital out B
high
Any output with ‘digital output 2’
selected is high (closed).
[40]
Set digital out C
high
Any output with ‘digital output 3’
selected is high (closed).
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
101