6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling
value that corresponds to the high
voltage/high current value set in
and
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 -
10.000 s]
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 54.
A high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
6-27 Terminal 54 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live
Zero monitoring. E.g. to be used if the analog
outputs are used as part of a de-central I/O system
(e.g. when not as part of any frequency converter
related control functions, but feeding a Building
Management System with data).
[0]
Disabled
[1]
*
Enabled
3.8.4 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) placed on option module MCB 101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par. 6-31
V]
Sets the analog input scaling value to
correspond to the low reference/
feedback value (set in
).
6-31 Terminal X30/11 High Voltage
Range:
Function:
10.00 V
*
[par. 6-30 -
10.00 V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value (set in
).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling value
to correspond to the low voltage
value (set in
).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling
value to correspond to the high
voltage value (set in
6-31 Terminal X30/11 High
Voltage
).
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10.000
s]
A 1
st
order digital low pass filter time
constant for suppressing electrical noise
on terminal X30/11.
6-36 Term. X30/11 Filter Time Constant
cannot be changed while the motor is
running.
6-37 Term. X30/11 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live
Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system
(e.g. when not part of any frequency converter
related control functions, but feeding a Building
Management System with data).
[0]
*
Disabled
[1]
*
Enabled
3.8.5 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) placed on option module MCB 101.
6-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par. 6-41
V]
Sets the analog input scaling value to
correspond to the low reference/
feedback value set in
6-41 Terminal X30/12 High Voltage
Range:
Function:
10.00 V
*
[par. 6-40 -
10.00 V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value set in
.
Parameter Description
VLT
®
HVAC Drive Programming Guide
70
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3