VLT
®
2800 Series
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Coasting
1
1
Motor running
503 Quick-stop
(Q STOP SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is running
and when it is in Quick-stop mode, when each of
the following is selected:
Digital input
[0],
Serial
port
[1],
Logic and
[2] or
Logic or
[3].
NB!:
Note that
Quick-stop inverse
and Bit 04 in
the control word are active at logic
’
0
’
.
Digital input
[0]
Dig. input
Serial port
Function
0
0
Quick-stop
0
1
Quick-stop
1
0
Motor running
1
1
Motor running
Serial port
[1]
Dig. input
Serial port
Function
0
0
Quick-stop
0
1
Motor running
1
0
Quick-stop
1
1
Motor running
Logic and
[2]
Dig. input
Serial port
Function
0
0
Quick-stop
0
1
Motor running
1
0
Motor running
1
1
Motor running
Logic or
[3]
Dig. input
Serial port
Function
0
0
Quick-stop
0
1
Quick-stop
1
0
Quick-stop
1
1
Motor running
504 DC brake
(DC BRAKE SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is
running and the DC braking when each of the
following is selected
Digital input
[0],
Serial port
[1],
Logic and
[2] or
Logic or
[3].
NB!:
Note that
DC braking inverse
and Bit 02 in
the control word are active at logic
’
0
’
.
Digital input
[0]
Dig. input
Ser. port
Function
0
0
DC braking
0
1
DC braking
1
0
Motor running
1
1
Motor running
Serial port
[1]
Dig. input
Ser. port
Function
0
0
DC braking
0
1
Motor running
1
0
DC braking
1
1
Motor running
Logic and
[2]
Dig. input
Ser. port
Function
0
0
DC braking
0
1
Motor running
1
0
Motor running
1
1
Motor running
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
120