VLT
®
2800 Series
■
Operation & Display
001 Language
(LANGUAGE)
Value:
✭
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Function:
This parameter is used to choose the language
to be shown in the display whenever the LCP
control unit is connected.
Description of choice:
There is a choice of the languages shown.
The factory setting may vary.
002 Local/remote operation
(OPERATION SITE)
Value:
✭
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
There is a choice of two different modes of operation
of the frequency converter;
Remote operation
[0] or
Local operation
[1]. See also parameter 013
Local
control
if
Local operation
[1] is selected.
Description of choice:
If
Remote operation
[0] is selected, the frequency
converter is controlled via:
1. the control terminals or via serial communication.
2. the [START] key. This cannot, however, override
stop commands transmitted via the digital
inputs or via serial communication.
3. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If
Local operation
[1], is selected, the frequency
converter is controlled via:
1. the [START] key. This cannot, however, override
stop commands via the digital inputs (see
parameter 013
Local control
).
2. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3. the [FWD/REV] key, on the condition that is has
been selected as active in parameter 016
Local
reversing
, and that parameter 013
Local control
is set at
Local control and open loop
[1] or
Local
control as parameter 100
[3]. Parameter 200
Output frequency range
is set at
Both directions
.
4. parameter 003
Local reference
where the reference
can be set using the [+] and [-] keys.
5. an external control command that can be
connected to the digital inputs (see parameter
013
Local control
).
NB!:
The [JOG] and [FWD/REV] keys are located
on the LCP control unit.
003 Local reference
(LOCAL REFERENCE)
Value:
Par. 013
Local control
must be set to [1] or [2]:
0 - f
MAX
(par.
202)
✭
50 Hz
Par. 013
Local control
must be set to [3] or [4].
Ref
MIN
- Ref
MAX
(par. 204-205)
✭
0,0
Function:
In this parameter, the local reference can be set
manually. The unit of the local reference depends on the
configuration selected in parameter 100
Configuration
.
Description of choice:
In order to protect the local reference, parameter
002
Local/remote operation
must be set to
Local operation
[1]. Local reference cannot be
set via serial communication.
■
Setup configuration
There is a choice of four Setups (parameter Setups),
which can be programmed independently of one
another. The active Setup can be selected in
parameter 004
Active Setup
. When an LCP 2 control
unit is connected, the active Setup number will be
appear in the display under "Setup". It is also possible
to preset the frequency converter to
Multisetup
, so that
it is possible to shift Setups using the digital inputs
or serial communication. Setup shift can be used in
a plant in which, for example, one Setup is used for
daytime operation and another one at night time.
In parameter 006
Setup copying
it is possible to
copy from one Setup to another. Using parameter
007
LCP copy
all Setups can be transferred from
one frequency converter to another by moving the
✭
= factory setting. () = display text [] = value for use in communication via serial communication port