MAGNET POWER SUPPLY SYSTEM 7000
23
DANFYSIK A/S - DK 4040 JYLLINGE - DENMARK.
4.1.1
SYSTEM 7000 Interface specification:
SYSTEM 7000 has following external connections:
- Analogue Interface, D-sub 9 pole female
- Digital Interface, D-sub 25 pole female
- Parallel unit Master, top position connector D-sub 25 pole female
- Parallel unit Slave, bottom position connector D-sub 25 pole female
- AC main input, 3 phase, Neutral and Earth
- AC Control input
- Earth Screw
- MPS Status, Amphenol 4 pole series C091B female
- Current output
- External trig (for use with Ramp or fast ADC) 4 pole
- External interlocks, Weidmuller 151-096, 8 pole
- Rack Fan, Weidmuller 151-096, 2 pole
- Factory program 6 pole
Connector ANALOG:
Analogue status and analogue set value interface.
Pin no:
Name
I/O
Description & Specification
1
Measured Current Error
O
Output is 5V per 1% in difference between output
current and SET current.
2
Measured Voltage
O
Output is 10V if output voltage is 35V or 75V. This
depends on dip switch setting.
3
Measured Current
O
Output is 10V for 100% output current 20A one unit
and 40A when two units are in parallel and etc.
4
Current Setpoint readback O
Output is equal to SET value.
5
Current Setpoint
I
Input setponit, 10V equal to 20A for one unit and 40A
when two units are in parallel and etc.
6 Measured
Shield
O
7 Measured
RTN
O
8 Setpoint
Shield
I
9 Setpoint
RTN
I