MAGNET POWER SUPPLY SYSTEM 7000
35
DANFYSIK A/S - DK 4040 JYLLINGE - DENMARK.
4.3.7
Converter Over Voltage Interlock
If Converter voltage rises above app. 100V, interlock is activated.
The window span (R828, R829, R833, R834, R837 and R839) is calculated to 100V.
Due to limit in Interface Interlock lines, the Converter OV Interlock is not represented separate.
Summery is activated, but optional Converter OV is OR’ed to the Output OV Interlock.
4.3.8
Over Temperature Interlock
K801 is an 85 degrees C thermal sensor used on the Power Amplifier heat sink.
4.3.9
PS Fan Fault Interlock
If the PS Fan is short or open circuit, interlock is activated.
The fuse F801 will blow, if the Fan makes a short circuit. When the current is zero, interlock is
activated.
PS Fan interlock is bypassed when the Fan is powered up, to avoid interlock.
4.3.10
Ground Fault Interlock
Output ground is connected to chassis through a 1A fuse. Only the Master is connected to
chassis. This is controlled by the relay, K802.
The detector circuit is built upon U808. If the Ground-Fuse blows, the detector circuit will
detect a voltage between Output ground and chassis and interlock is activated.