Until main power is disconnected externally, dangerous voltages may is still be
present on the input terminals, EMI filter, Q1 input side and F4 input side!
Introduction
Servicing DANFYSIK Magnet Power Supplies is only allowed by trained and qualified personal.
DANGER!
Dangerous voltages capable of causing loss of life are present inside this
Magnet Power Supply. Use extreme caution when accessing, handling, testing
and adjusting.
CAUTION!
Only qualified personnel are allowed to maintain this equipment.
DANGER! ELECTRIC SHOCK HAZARD!
Disconnect power at switch board before attempting to work on the Magnet
Power Supply. High voltages are present at the terminals and within the Magnet
Power Supply for up to 10 minutes after disconnection of the electrical supply.
Always ensure by using a suitable measuring device that no voltage is present
prior to commencing work.
Preventive maintenance
In a normal operating environment, perform the following tasks at one year intervals:
•
Clean all fan protection grills.
•
Vacuum clean the openings in the cabinet and all heat sinks mounted on printed circuit
boards to ensure a normal flow of cooling air.
•
Check that all screw connections to the primary and from the secondary of the transformer
are tightened.
•
Check that connections from the secondary of the transformer to the output terminals are
tightened. (I.e. cable and bus bars carrying heavy current).
•
Check that the water-flow switch works correct.
•
Check that external interlocks are functioning.
•
Check function of door interlocks.
In dusty or dirty environments the above-mentioned points should be performed more often.
•
Visually inspect the power supply for overheated components or other suspicious signs.
Adjustment and calibration
To be described