MAGNET POWER SUPPLY SYSTEM 9100
25
DANFYSIK A/S - DENMARK.
Be aware when changing the Baud rates. Wrong setting may cause communication loss.
Modifying a baud rate with the HW switches or through the appropriate SW command, will
first take effect after a reset. At the remote line, use command ESC<CPURESET to make a
reset.
For switch settings following terminology will be used.
S
W
4
ON
SIGNATURE USED:
OFF
DON‟T CARE
DON‟T CHANGE
S
W
3
ON
ON
1 2 3 4
1 2 3 4 5 6 7 8
D13 - D20
D24 - D30
Setup
SETUP
S
Reset
Interlock LED indications (Mode 0)
red LED
LED
13
LED
14
LED
15
LED
16
LED
17
LED
18
LED
19
LED
20
Status
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
NO interlocks
ON
Overvoltage
ON
Overcurrent
ON
Phase failure
ON
Fault UV/Temp
ON
Ground Leak
ON
Fan
ON
External interlock 1&2
ON
External interlock 3&4
If all interlocks occur, all 8 red LEDs will illuminate.
When the interlocks are removed, the interlock LED indications can be reset by pressing the
RESET button on the display board which means that the red LEDs turn off.