MAGNET POWER SUPPLY SYSTEM 9100
61
DANFYSIK A/S - DENMARK.
REMOTE CONTROL X7 (D-SUB 25 Pole):
Remote, RS232, RS422, RS485 DB25 serial line Interface
Pin no: Name
I/O
Description & Specification
2
Tx
O
RS232 Transmitter line
3
Rx
I
RS232 Receiver line
7
RETURN
I/O
Return line for RS232
9
Tx High
O
RS422/485 Transmitter positive line
10
Tx Low
O
RS422/485 Transmitter negative line
11
Rx High
I
RS422/485 Receiver positive line
12
Rx Low
I
RS422/485 Receiver negative line
13
VCC
O
Supply v5VDC
Connector X9 (pin 1-4) X8 (pin 6-10) X112 (pin 12-16):
16-pol connector for SYNC, POLARITY, INTERLOCKS and 24V DC supply:
Pin no: Name
I/O
Description & Specification
1
SYNC+O
O
Open collector output up to 24V/100mA. Active in minimum 2.5ms when a ramp
profile has been triggered.
2
SYNC-O
O
Return line for SYNC +O
3
SYNC-I
I
Return wire for pin 4
4
SYNC+I
I
Applying a 15 to 25 V signal between pin 3 and 4 will start the SW ramp profile if
armed.
5
+24V_ EXT
O
+24V
6
POL_NORM
7
POL_INV
8
POL_GND
9
POLSHIFT
10
POL+24V
11
+24V_EXT_GND
Return for +24V_EXT
12
+24V Input
I
Supply input for external interlocks.
13
EXT INTERLOCK 3
I
Optically isolated input. Pull to +24V ground to disable.
14
EXT INTERLOCK 2
I
Optically isolated input. Pull to+24V ground to disable.
15
EXT INTERLOCK 1
I
Optically isolated input. Pull to +24V ground to disable.
16
EXT INTERLOCK 0
I
Optically isolated input. Pull to +24V ground to disable.
Fuseholder F1:
Fuse for control power
Pin no: Name
I/O
Description & Specification
F1
Fuse for control power (2A/250V)