MAGNET POWER SUPPLY SYSTEM 9100
62
DANFYSIK A/S - DENMARK.
6
Maintenance
6.1
Introduction
Servicing DANFYSIK Magnet Power Supply should be attempted only by trained and
qualified personal.
Dangerous voltages capable of causing loss of life are present inside this power supply. Use
extreme caution when accessing, handling, testing and adjusting.
6.2
Preventive maintenance
In normal operating environment, perform the following tasks at one year intervals.:
-
Clean all fan protection grilles.
-
Vacuum the openings in the cabinet and all heat sinks mounted on printed circuit boards
to ensure a normal flow of cooling air.
-
Check that screw connections from the output terminals are tightened.
In dusty or dirty environments the above-mentioned points should be performed more often.
-
Inspect visually the power supply for components that have been overheated or other
suspicious sign.
In high radiation environment, performances of following tasks are recommended at one year
intervals:
-
Replace all ICs mounted in sockets on the printed circuit boards.
-
Printed circuit boards with ICs mounted without sockets should be replaced.
6.3
Adjustment and calibration
This power supply does not need any regular adjustment or calibration.