19
Installation Method:
Users to install the external threads coated with an appropriate amount of sealant to seal
can also choose other sealing methods.
Out of gas regulator valve thread must match the connecting thread with the gas.
Regulator valve installation location must be perpendicular.
After installation, open the gas source switch, and check valvebody with soap and water
connections for leaks.
The gas kinds of conversion method:
Regulator valve factory set to natural gas or liquefied petroleum gas for conversion of
gas species, with special tools counterclockwise to open the top cover (Figure 1).
Remove the adapter from the top cover (Figure 2).
Ripped out the adapter inverted Replace the top cover (Figure 3).
Inverted the assembled adapters top cover, replace the regulator valve (Figure 4) .
Figure 1
Factory-set state
Figure 2
Figure 3
Figure 4
o
Operating Temperature:-20
℃
~60
℃
.
o
Inlet pressure setting: of natural gas 6 in.wc / liquefied gas 11
in.wc of.
The performance parameters of the following table:
o
Natural gas and liquefied petroleum gas conversion
function,
need to be set manually.