Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
Make sure the power is isolated from the circuit.
2. Remove the 20mm knockout from the end of the lighting batten.
3. Making reference to diagram A: Remove the 20mm thread from the
PIR and insert it through the 20mm knockout hole with the thread
facing outwards
4. Feed the trailing wires through the thread and with the PIR facing
downwards tighten the 20mm thread.
5. The trailing wires should be connected to the ballast as:
Brown - Live supply. Blue - Neutral supply. White - Switched Line to ballast.
6. Once the wiring has been completed and verified, switch on the supply
and test the operation.
Set-up
7. When powered up, (after 1 minute stabilisation time) turn lux pot
fully clockwise and time pot fully anticlockwise.
8. Press the button for approximately 0.5s. The LED will go green indi
-
cating the LUX cell is active. (Or press and hold button for approx. 4
seconds – LED goes RED indicating Lux cell INACTIVE). Repeating
these steps will toggle the functionality.
9. If lux cell active, vacate area until PIR switch switches the load off
(should be after 10 seconds).
10. With the LUX as desired on desktop from daylight ONLY (no artificial
light), wind the lux pot anticlockwise whilst waving your hand in front
of the PIR cell. When the PIR switches the load ON, stop turning the
pot. The Lux inhibit level is now set.
11. Turn the PIR time to the desired timeout.
To light
fitting
ballast
C: Lux
adjustment
D: Time
adjustment
Dual colour LED
RED - PIR active, Photocell inactive
GREEN - PIR and Photocell override ON (passive LUX)
Lux Cell
Mode
PIR Lens
Time
delay
setting
Lux setting
Lux cell
PIR head - key components
Precondition
Power-up Condition
Lux Cell Inactive
Relay OFF
Lux Cell Inactive
Relay comes ON for 1 Min. After 1 min. ready for detection.
Lux Cell Active
Relay ON
Lux Cell Active
Relay stays ON for 1 Min. After 1 min. ready for detection.
Lux Cell Active
Relay OFF
Lux Cell Active
Relay comes ON for 1 Min. After 1 min. ready for detection.
Lux Cell Inactive
Relay ON
Lux Cell Inactive
Relay stays ON for 1 Min. After 1 min. ready for detection.