Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: The CEFLA PIR DALIP should be installed to achieve
correct coverage of the area, see diagram A. Avoid locating this product
where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources.
3. Make sure the power is isolated from the circuit.
The PIR should be connected as shown in diagram E:
Thick wire
Thin wire (DALI control lines)
Brown
L
Live in
Red / Blue Polarity independant
Blue
N
Neutral in
Black
SL Switched Line out
White
SW
1
Switch / Input
Start-up mode
When the PIR is powered up, it will switch on the load for 1 minute, the
load will then switch off and the PIR will enter its Operating Mode.
The LUX adjuster spindle on the side of the PIR is used to regulate the
automatic daylight linked dimming function lux level (see diagram D
opposite). This should be adjusted in situ by rotating the LUX adjuster
slowly anticlockwise
(+ to -) so that the desired level of brightness is achieved under the
luminarie(s) being controlled.
If the LUX spindle is quickly turned the lights can be dimmed up and down
to the required LUX level by further rotation of the LUX spindle. Once the
correct level is achieved and there has been no further adjustment to the
LUX spindle,
CEFLA PIR DALIP
will go through a 30 second delay before
the automatic closed loop control will start.
CEFLA PIR DALIP incorporates a fixed 20 second fade rate from maximum
to the set back level.
Sensitivity
CEFLA PIR DALIP incorporates a sensitivity adjuster, labelled ‘SENS’, to
reduce the range of detection from 100% to 50% in 9 steps
(see diagram
C opposite).
Clearance hole
63 or 64mm (2.5") diameter
Springs can either be left closed (down
the side of the product) or opened out.
RUN ON
min
max
LUX
min
max
Typical settings
INFINITE
30m
20m
15m
10m
5m
0s
1m
2m
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
For optimum coverage
recommended mounting
height: 2.4 to 5m
B: Detection diagram
E: Wiring diagram,
CEFLA PIR DALIP controlling several DALI dimmable ballasts
D: Adjusting LUX and RUN-ON
L
N
DALI
Ballast
CEFLA PIR DALIP
DALI Control Lines
DALI
Ballast
Optional
other load
230 VAC
SL
L
N
Mains
rated
retractive
wall switch
or rocker
wall switch
(toggled)
SW
1
TIME
min
max
SENS
min
max
Typical settings
40m
20m
10m
5m
2.5m
80s
10s
20s
40s
50%
100%
C: Adjusting SENSITIVITY and TIME
A: Detection diagram
Time / Run-on / Lux set up