27
EN
Important!
If the dehumidifier is not functioning correctly, shut it down immediately!
Fault finding
Use this table to localize and solve a possible problem or fault:
Fault
Possible cause
Solution
• The dehumidifier
does not work
• no light in the LEDs
on the display
-
• Check the external
fuses
• Check the power
supply to the unit
• The compressor does not
work
• the display shows wrong
type
The compressor has stopped
automatically caused by a
too high temperature on the
condenser
If the unit does not start again
after 45 minutes, check the
following:
• Check that the fan(s) is
running
• Check if the filter in the duct
kit is dirty, clean if necessary.
• Check if the condenser coil
is dirty
• Check if the room tempera-
ture is higher than 36 °C. If the
room temperature is higher
than 36 °C, the unit must be
stopped
• Check that the duct
openings are not covered
• The dehumidifier does not
work
Check the built-in or the exter-
nal hygrostat, if any, by setting
it to a low relative humidity,
e.g. 10 – 20 %RH.
If the unit still does not start,
check the built-in or external
hygrostat for defects.
More help
If you cannot find the reason for the fault, switch off the unit immediately in order to prevent
further damage.
Contact a service technician or a Dantherm representative.
Fault finding guide
Summary of Contents for 351510
Page 9: ...9...
Page 14: ...14 EN CDP 40 50 70 CDP 40T 50T 70T Dimensions...
Page 18: ...18 EN CDP 40T 50T 70T Mounting and installation instructions CDP T 1...
Page 19: ...19 EN Mounting and installation instructions CDP T Continued CDP 40T 2a CDP 50T 2b CDP 70T 2c...
Page 20: ...20 EN 3 Mounting and installation instructions CDP T Continued...
Page 35: ...35 EN Overview Accessories Water heating coil for CDP dehumidifier...
Page 50: ...50 EN Spare parts 1 4 5 6 7 15 10 14 20 19 22 13 12 8 24 23 26 16 21 11 17 18 9 3 2 27 28 25...