45
EN
Evaporator sensor fail
If evaporator sensor is defect, then “EVAP” code will be shown when pressing UP or DOWN
during screen shows Sensor fail code “SEnS”.
If Evaporator sensor ok, then no “EVAP” code shall be shown.
If no buttons pressed within 10 seconds then screen will show “SEnS” fail again.
It is not possible to enter menu setup to modify set point.
RH/T sensor fail
If RH/T sensor is defect, then “rh°t” code will be shown when pressing UP or DOWN during
screen shows Sensor fail code “SEnS”.
If RH/T sensor ok, then no “rh°t” code shall be shown.
If no buttons pressed within 10 seconds then screen will show “SEnS” fail again.
It is not possible to enter menu setup to modify set point.
Low pressure fail
Dehumidifier stopped because of Low Pressure detection.
Fail can not be dismissed from DRC1.
It is not possible to enter menu setup to modify set point.
Alarms continued
Press to see which sensor
is defect.
Press to see which sensor
is defect.
Press to see which sensor
is defect.
Press to see which sensor
is defect.
Summary of Contents for 351510
Page 9: ...9...
Page 14: ...14 EN CDP 40 50 70 CDP 40T 50T 70T Dimensions...
Page 18: ...18 EN CDP 40T 50T 70T Mounting and installation instructions CDP T 1...
Page 19: ...19 EN Mounting and installation instructions CDP T Continued CDP 40T 2a CDP 50T 2b CDP 70T 2c...
Page 20: ...20 EN 3 Mounting and installation instructions CDP T Continued...
Page 35: ...35 EN Overview Accessories Water heating coil for CDP dehumidifier...
Page 50: ...50 EN Spare parts 1 4 5 6 7 15 10 14 20 19 22 13 12 8 24 23 26 16 21 11 17 18 9 3 2 27 28 25...