28
Preventive maintenance,
continued
Annual preventive
maintenance
Follow this procedure to carry out the annual preventive maintenance:
Caution
When dismounting the front and the top cover you are breaking the EMC seal. When
remounting the unit be aware that the EMC seal is intact and restored properly.
Step
Action
1
Perform the daily and monthly maintenance, see above
2
Place the unit on a surface where the front frame can be free
3
Inspect the evaporator and condenser coils.
See the drawing below and follow the following steps to make access to the
coils:
4
Dismount the front frame by unscrewing 16 torx 20 screws
c
to get access
to the filter
5
Dismount all 21 screws on the top cover
d
, top, sides and back
6
Inspect the evaporator and condenser coils. If they are dirty, then clean with
a hoover or wash with warm soap water and a brush
Lift up the internal fan module 7-10 cm to get better access to the evaporator
Before being able to lift the fan module you need to unscrew 2 screws be-
tween the fan house and the coils
e
7
Clean the drip tray
8
Inspect and if necessary clean the radial wheels in the two fans
9
Follow the above steps just in reverse order to remount the unit
d
c
e