34
Fault finding guide,
continued
Fault finding,
con-
tinued
Problem
c
Cause
d
Action
e
No heating action possi-
ble.
Power light is green.
Heat indicator lamp is
red.
Overheat thermostat failure
or loose electrical connec-
tion
Allow temperature to drop
before pressing the reset
button on top of ACU
Fans stop running.
Fan light is red
Internal temperature protec-
tion in either condenser or
evaporator fan motor has
cut-out
Check for blocked fan(s).
Check for loose connec-
tors