26
Display,
continued
Meaning of the
LEDs,
continued
LEDs
Description
+
+
The constant green Lightning indicates that power is con-
nected to the unit. The Drop and the Triangle are flashing on
and off in green and red, respectively, to indicate that the
condenser sensor has sensed a failure.
If the low-pressure pressostat registers a too low pressure in
the cooling circuit, caused by a too low temperature across
the evaporator, the unit will be stopped until the required
pressure has been re-established and the low-pressure
pressostat then switches on the unit again.
After resetting, the Triangle is switched off and the Drop
continues to flash on and off. The Lightning is constantly
green.
+
When the Drop flashes on and off in green and the Lighting
is constant green, this indicates that the unit is working but
there has been a failure on the unit through the LP presso-
stat.
The flashing Drop is switched off by turning the unit OFF and
ON on the main switch.
+
+
A constantly green Lightning indicates that power is on. The
Drop and the Triangle LEDs flash on and off in green and
lights up constantly in red, respectively, to indicate that the
HP pressostat or the thermal relay has switched off the com-
pressor and that the unit has been cut off.
If the high-pressure pressostat has registered a too high
pressure in the cooling circuit, caused by a too high temper-
ature across the condenser, the compressor will be switched
off and the unit stops. The thermal relay also switches off
the compressor and stops the unit, if the temperature in the
compressor gets too high. If the unit switches off again after
having reset the HP pressostat and the thermal relay, the unit
must be checked by a service engineer. (See section 7. Faults
and how to remedy them). The flashing Drop is switched off
by turning the unit OFF and ON on the main switch.
Continued overleaf
Summary of Contents for cdp 165
Page 1: ...CDP 75 MKII 125 MKII 165 Service manual Rev 1 7...
Page 2: ......
Page 74: ...72 RU 2 5 RU 72 73 75 77 o 80 82 87 88 89...
Page 77: ...75 087762 Version 1 7 03 06 2021 CDP 75 125 MKII 165 CDP 75 MK II 125 MK II 165 5...
Page 79: ...77 087762 Version 1 7 03 06 2021...
Page 80: ...78 OFF ON 7...
Page 81: ...79 087762 Version 1 7 03 06 2021 u1080...
Page 82: ...80 o 12 1 3 4 a 12 1 5 6 2 5 6...
Page 84: ...82 CDP 75 MK II 125 MK II 16 CDP 75 MK II CDP 125 MK II t 3 4 0 5 2 u1086...
Page 87: ...85 087762 Version 1 7 03 06 2021 CDP 75 MK II 125 MK II 165 15 PEX 128 IN OUT 141...
Page 89: ...87 087762 Version 1 7 03 06 2021 1 2 3 1 1 2 3 1 2 3 4 5...
Page 90: ...88 20 38 10 20 Dantherm...
Page 191: ......