28
Hygrostat and other control options
Hygrostat
The control is prepared for connection of a hygrostat which is placed in the room to be
dehumidified or in the supply air duct
–
(air inlet).
Hygrostat is available as accessory.
Connection of
hygrostat
Please follow this procedure to connect a hygrostat.
The outlet for the hygrostat is 12 V.
Step
Action
1
The hygrostat is connected to the terminals 3 and 4 after having taken away
the bridge
Room thermostat
The control is prepared for connection of a room thermostat which is placed in the
room to be dehumidified or in the supply air duct
–
(air inlet).
Room thermostat is available as accessory.
Connection of room
thermostat
Please follow this procedure to connect a room thermostat.
The outlet for the room thermostat is 12 V.
Step
Action
1
The thermostat is connected to the terminals 5 and 6 after having taken away
the bridge
Continued overleaf
Summary of Contents for cdp 165
Page 1: ...CDP 75 MKII 125 MKII 165 Service manual Rev 1 7...
Page 2: ......
Page 74: ...72 RU 2 5 RU 72 73 75 77 o 80 82 87 88 89...
Page 77: ...75 087762 Version 1 7 03 06 2021 CDP 75 125 MKII 165 CDP 75 MK II 125 MK II 165 5...
Page 79: ...77 087762 Version 1 7 03 06 2021...
Page 80: ...78 OFF ON 7...
Page 81: ...79 087762 Version 1 7 03 06 2021 u1080...
Page 82: ...80 o 12 1 3 4 a 12 1 5 6 2 5 6...
Page 84: ...82 CDP 75 MK II 125 MK II 16 CDP 75 MK II CDP 125 MK II t 3 4 0 5 2 u1086...
Page 87: ...85 087762 Version 1 7 03 06 2021 CDP 75 MK II 125 MK II 165 15 PEX 128 IN OUT 141...
Page 89: ...87 087762 Version 1 7 03 06 2021 1 2 3 1 1 2 3 1 2 3 4 5...
Page 90: ...88 20 38 10 20 Dantherm...
Page 191: ......