1. GENERAL
3
1. General
1.1 Introduction
The DanX - AF equipment is designed mainly for the use for ventilation, humidity and
temperature control in private and public swimming pool areas. The use of the unit includes
the required inspection and maintenance for these units, which is described in the back of
this manual.
Unloading, transportation, assembly, connecting of the DanX modules should only being
carried out by trained specialists
or by people supervised by authorized staff. It is the
responsibility of the fitter to read and understand this guide and other given information.
1.2 Foundation for the unit
The DanX unit must be installed in a location that meets the following requirements:
•
The supporting structure must be flat and stable.
•
The supporting structure must be able to bear the weight of the unit.
•
The deflection of the substructure should be max. 1 mm/m.
•
For the connection of the condensate drain, it is necessary that the height between
condense outlet of the unit and the substructure is at least the required height for the
water trap.
•
If the unit is mounted on a roof, the bearing ability of the roof and its support structure
has to be examined.
1.3 Minimum distances
For the operation, maintenance and servicing of parts as heating coils, dampers and others
a minimum clearance between inspection side of the unit and the rear wall should be the
width of the unit. It is recommended also have a minimum clearance between the rear wall
and the rear of the unit providing at least 600 mm for service and installation purposes.
Model
W min [mm]
Model
W min [mm]
AF 3/6
900
AF 7/14 s
1900
AF 5/10
1400
AF 12/24
2200
AF 5/10 s
1400
AF 12/24 s
2200
AF 7/14
1900