34
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Installation
: Mounting the device
3
Connect the drain hose to the
drain outlet in use and secure the
connection with a hose clamp.
4
The drain hose must be fitted
with a water trap of min. 100 mm
(option A or B).
•
Route the hose to a drain and
ensure that it is not exposed
to frost.
•
Fill the water trap with min.
0.5 L water.
5
HCV 400/460 only
•
Mount the cable clamp in the
hole in the bottom of the unit
•
Pass the drain hose through
the cable clamp to form a
water trap.
Material damage (e .g . water damage)
Heat recovery of air with a high moisture content leads to condensation in the heat ex-
changer. Condensate must be led into a drain, as it otherwise may damage the floor under
the unit.
•
Make sure that the drain hose is installed according to the current operating mode.
•
Check the water trap regularly, especially during the summer, and make sure it is filled
with water as recommended.
A
B
Warning
Caution
WARNING
Summary of Contents for HCV 300
Page 1: ...HCV 300 400 460 500 700 MANUAL en Rev 1 2 2021 W03 4...
Page 2: ......
Page 58: ......
Page 59: ......