51
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Appendix
: Technical data
en
Appendix
Technical data
Specification
Abbr .
Unit
HCV 400
P1
HCV 400
P2
HCV 400
E1
Operating range (min. @ 50Pa - max.
@ 100Pa)
V
m3/h
80 to 250 50 to 240 50 to 240
EN 13141-7 reference flow (@ 50Pa)
V
REF
m3/h
175
168
168
Performance
Temperature efficiency in accordance
with EN13141-7
h
SUP
%
from 91%
to 97%
from 89%
to 96%
from 79%
to 94%
Specific power consumption in accor-
dance with EN13141-7 (@ ref. flow)
SEL/SPI
W/(m
3
/h)
0.23
0.19
0.20
Leakage (external and internal) in
accordance with EN13141-7
-
%
< 2 (Class A1)
Filters in accordance with ISO16890 /
EN779
-
-
ISO Coarse 75% / G4
(optional: ePM1 55% / F7)
Ambient temperature for installation
t
SURR
°C
from +12 to +50
Outdoor temperature range without
installed preheater
t
ODA
°C
from -12 to +50
Outdoor temperature range with
installed preheater
t
ODA
°C
from -25 to +50
Maximum absolute humidity in
extract air
x
g/kg
10
Cabinet:
Exterior dimensions (without wall
bracket)
W x H x D
mm
540 x 1051 x 549
Spigots/duct connections
Ø
mm
160 - female
Weight
m
kg
39
Thermal conductivity -
polystyrene insulation
l
W/(mK)
0.031
Heat transfer coefficient -
polystyrene insulation
U
W/
(m
2
K)
< 1
Fire class - polystyrene insulation
-
-
DIN 4102-1 Class B2
EN 13501 Class E
Drainage hose
Ø/length " / m
3/4” – 1 m
Cabinet colour
RAL
-
9016
Electrical
Voltage
U
V
230
Max. power consumption (without/
with preheater)
P
W
170/1,570
Frequency
f
Hz
50
IP class
class
-
21
* The use of the preheating coil is recommended at outdoor temperatures below -3°C to
ensure balanced operation
Data sheet
HCV 400
Summary of Contents for HCV 300