U:\Manuals\EFC\EFC2V2TC
-EN-.pdf
15/15 2008-11-13
Test Report: ACUE CS1,
continued
Test of temperature
sensors
Fire & smoke alarm
If the display show a “-“ this means that the sensors is out of range. What the sensor
indicate, warm or cold,
indicates with the lamps LOW TEMP. ALARM respectively HIGH TEMP. ALARM
following:
LOW TEMP. ALARM: The sensor indicate very cold (
short-circuit
).
HIGH TEMP. ALARM: The sensor indicate very hot. (
cut-off or not connected
).
To make the test of the sensors as reliable as possible, please make no manual
steps.
After the self test, the Fire and smoke alarm (if applicable) shall be done.
Alarm
Action
Check
Fire & smoke alarm Activate the smoke detector.
Check that everything is stopped: Fan, Heater,
AC, and that the dampers are closed. The display
shows “Fire Alarm”.
Sign the protocol
Test report data
Site – station designation/no
Test date
Test made by
Signature
Company
Documentation
Send a copy of the protocol to the responsible operator.