61
0
4
5
8
9
3
•
V
e
rsi
o
n
2
.3
•
1
6
.0
3
.2
0
1
2
5.2 Technical data, MHX 85 heat exchanger
General data
The general technical data on the heat exchanger is shown in the following table:
Specification
Designation
Value
Maximum ambient temperature
(ETS 300 019-1-4)
°C
40
Minimum ambient temperature
(ETS 300 019-1-4)
°C
-30
Max. cabinet return temperature
°C
60
Specific cooling capacity incl. Solar
W/K
85 (max)
Voltage supply (range)
VDC
52 (40-56)
Sound pressure (1m) as stand alone (max power)
When mounted in double walled door significant
reduction on this can be achieved. Lower max
performance will also give lower noise emissions.
dB(A)
68
Air flow internal @ max. cooling,
~60%
m
3
/h
400
Air flow external @ max. cooling
~60%
m
3
/h
400
Service, recommended preventive maintenance
intervals
months
6
Operating range - humidity
%RF
5-99
non condensing
environment
Operating range
– temperature
°C
÷ 30
– 70
Power supply
V DC
40-60
Nominal 52
Power consumption
(48 VDC) @ max. cooling
W
120
Performance
W/K
85
Weight
kg
20
Dimensions (W × D × H)
mm
1500 × 450 × 155
Safety class, mounted on door
IP
55
Continued overleaf