background image

·

Purpose of the Manual

Through the manual, you can understand the structure, installation specifications, control principles, process flow and 
operation methods of the cabinet-type dehumidifier.

·

 Knowledge Required

You need to have knowledge of automatic control and air handling to understand the manual.

·

Contents Included

The manual explains in detail the functions, operation, daily maintenance and troubleshooting of the cabinet-type dehumidifier.

·

All rights reserved

Copying of this manual, or part of it, is forbidden without prior written permission from 

DANVEX

.The warranty and technical 

support of this product are only valid in the country or region of purchase.

Foreword

UL/484-2014       American standard for Room air conditioners

ANSI/UL94         American standard for Safety of Flammability of Plastic Materials for Parts in Devices and Appliances

UL/969           American standard for marking and labeling systems used for permanent product identification 

UL/474-1993       American Safety Standard for Dehumidifiers

GB/T191-2008      China National Standard for Packaging - Pictorial Markings for Handling of Goods

ANSI/AHAM DH-1-2008   ANSI/AHAM Standard for dehumidifiers

This unit must be operated by trained professionals, otherwise it will cause casualties or property damage.

Please read and understand this manual thoroughly before operation to avoid damage to the unit or personal injury or death caused by 

misoperation.

Please contact the supplier or the manufacturer if there are any issues arises that are not stated in this manual.

Standards and Codes:

GB/4706.32-2004  China National Standard No. GB/4706.32-2004, Code of household and similar electrical appliances Particular 

requirements for heat Pumps, air-conditioner and dehumidifier

IEC 60335-2-40    International safety Standard for electric heat pumps, including sanitary hot water heat pumps, air-conditioners, and 

dehumidifiers incorporating sealed motor- compressors

Please keep this manual for later reference.

GB/T16803-2018   China National Standard No. GB/T16803-2018, Code of of heating, ventilating, air conditioning and air cleaning 

terminology 

GB/T2518        China National Standard No.GB/T2518, Code of of continuously hot-dip zinc and zinc alloy coated steel sheet 

GBJ16-87          China National Standard No.GBJ16-87, Code for fire protection of building design

GB/T19411-2003    China National Standard for dehumidifiers 

GB/T17791-2007    China National Standard No. GB/T17791-2007, Code of of Specification for seamless copper tube for air conditioning 

and refrigeration field service

GB/755-2000      China National Standard No. GB/755-2000, Code of of Rotating electrical machines--Rating and performance

GB/50016-2006   China National Standard No.GB/50016-2006, Code of Design on Building Fire Protection and Prevention

GB/50243-2002   China National Standard No. GB/50243-2002,Code of acceptance for construction quality of ventilation and air 

conditioning works

GB/50019-2003    China National Standard No. GB/50019-2003,Code for Design of Heating Ventilation and Air Conditioning

GB/50015-2019   China National Standard No. GB/50015-2019,Code for design of building water supply and drainage

GB/T7725-2004    China National Standard No. GB/T7725-2004, Code for room air conditioners 

GB/T18883-2002    China National Standard for indoor Air Quality Standard

NOTE

Warning

This symbol indicates the rules that must be followed! If it is not strictly followed, 
it may cause mild to moderate damage to the machine or signs of personal injury.

This symbol indicates actions that must be prohibited!! If not strictly followed, 
it may cause serious damage to the machine or personal injury or death.

When a problem occurs (such as a 
burning smell, etc.), please turn 
off the unit and unplug the power 
cord. (Cut off the power supply).

Please follow this manual for 
installation. Please read this manual 
carefully before running or servicing
the unit.

The space above the equipment 
installation is at least 50 cm, the 
rear and the left and right sides 
are at least 100 cm, and the front 
is at least 200 cm.

Before installation, please check 
whether the power cord used is 
consistent with the power required 
on the nameplate, and check the 
safety of the power supply.

Be sure to use special accessories 
and parts during installation. 
Otherwise, it may cause water 
leakage, electric shock, fire and 
other accidents.

The power connection of this unit 
adopts Y-type connection, and the 
diameter of the power cord should 
be large enough. If the power cord 
is damaged, in order to avoid danger,
the power cord should be replaced 
by the manufacturer or professionals.

Do not insert your fingers or objects 
into the air outlet or return air grille.

Do not start or stop the unit by 
pulling out the plug.

Do not allow children to operate 
the unit.

The unit can only be cleaned after 
shutting down and cutting off the 
power supply, otherwise you may 
get an electric shock or be injured.

The installation should be carried 
out by the seller or qualified 
professionals, please do not install 
the unit by yourself. Incorrect 
installation may cause accidents 
such as water leakage, electric 
shock or fire.

The unit should be grounded, and 
the power socket must be equipped 
with a ground wire to ensure that 
the machine is effectively grounded 
through the power socket to avoid 
the risk of electric shock. Do not 
connect the ground wire to gas 
pipes, water pipes, lightning rods or 
telephone wiring.

Drainage pipes should be installed 
correctly in accordance with the 
installation instructions to ensure 
proper drainage, and insulation 
measures should be taken to avoid 
condensation.Improper installation 
of pipes will cause water leakage.

Volatile liquids such as thinner or 
gasoline will damage the 
appearance of the unit. (Only use a 
soft dry cloth and a damp cloth 
dampened with a neutral detergent 
to clean the casing of the unit).

Once the unit is turned on, it must 
run for at least 5 minutes before it 
can be turned off, otherwise it will 
affect the compressor oil return.

Do not operate the unit with 
wet hands.

Do not pour or rinse the unit with 
water, otherwise it may cause 
malfunction or risk of electric shock.

When the unit is not used for a 
long time, please cut off the power 
supply of the unit.

After the unit is installed, electric 
leakage test should be carried out.

Do not repair the unit by yourself. 
Wrong maintenance will cause 
electric shock or fire.

Do not step on the unit, and do 
not place objects on or on the air 
inlet and outlet of the unit.

After installation, please check 
and confirm whether the 
connections of drain pipes, ducts 
and wires are correct to prevent 
water leakage, refrigerant leakage, 
electric shock or fire accidents.

Do not use or store flammable 
and explosive dangerous goods 
next to the unit. There should 
be at least 1.5m between the 
combustible surface and the unit.

For units using line control, 
the line controller store must 
be connected first, otherwise 
the line controller will be unusable.

DANVEX

 assumes no responsibility for personal injury or equipment damage caused by improper installation, commissioning, 

unnecessary maintenance, and failure to follow the regulations and instructions in this manual.

SPECIAL 

ACCESSORIES

SPECIAL

Summary of Contents for DEH-10K

Page 1: ...g Dehumidi ers Any questions please contact the manufacturer or dealer in time The repair and maintenance must be conducted by certi fed professionals Please read the manual carefully and in full befo...

Page 2: ...ates actions that must be prohibited If not strictly followed it may cause serious damage to the machine or personal injury or death When a problem occurs such as a burning smell etc please turn off t...

Page 3: ...eck 5 2 2 Wiring Check 5 2 3 Controller Check 6 Controller 6 1 General 6 1 1 Controller Terminals 6 1 2 Terminals Diagram 6 1 3 Controller s Interface 6 1 4 Parameters Setting 6 1 5 Icon 6 2 Controlle...

Page 4: ...peration of the compressor discharge high temperature and high pressure gas from the exhaust port enter the condenser for cooling It becomes a low temperature and high pressure gas intercepted by a ca...

Page 5: ...e of the equipment can be easily carried out The unique defrosting device effectively guarantees the reliable operation of the dehumidifier The fan adopts a centrifugal external rotor fan steel volute...

Page 6: ...ane fins the heat exchange efficiency is increased by 20 thus to reduce the unit size and weight The high quality thermal insulation material increases the thermal insulation effect by 15 2 5 5 Thrott...

Page 7: ...t in humidity temp sensor I IPX3 55DB 60DB 65DB Mitsubishi R410A copper tubes with blue hydrophilic coated aluminum fins SUS304 25 32 32 G4 PRE Filter 1122 600 1850mm DEH 5K DEH 10K 11KW 22KW 20A 40A...

Page 8: ...led indoors During installation there should be maintenance space at the rear of the dehumidification equipment to facilitate future inspection and maintenance of the equipment For cleaning and mainte...

Page 9: ...alled at a position 1 meter to 1 5 meters above the ground in order to detect representative water in the controlled area Flat or laid at the inspection point according to the design requirements The...

Page 10: ...tdoors to extract air as fresh air and then sent to a separate space after dehumidification such as paint spray room purification room 4 1 2 Ducting for Fresh Air Dry air Wet air Wet fresh air Dry fre...

Page 11: ...idifier unit must be carried out by professional staff Otherwise the company will not be responsible for all the consequences caused Check the installed air filter device to ensure it is in a clean st...

Page 12: ...um fan speed Fan coil valve Low fan speed Humidifier Compressor Air damper open Air damper close EC motor supply fan EC motor exhaust fan 12VDC RS485 A1 RS485 B1 RS485 A2 RS485 B2 GND FAN 1 FAN 2 L N...

Page 13: ...umidity press to raise humidity 1 changed each press Long press Short press simultaneously for 5 seconds to display the run time wait for 5 seconds to exit Short press to set the available code Press...

Page 14: ...es later after achieved the set humidity and temperature only for the available system working mode F01 2 high fan speed low fan speed available High fan speed low fan speed available when H04 1 F01 3...

Page 15: ...rror code is E01 It will resume operation after the error addressed The error code is E03 It will resume operation after the error addressed if there is RS485 1 communication failure only the fan keep...

Page 16: ...unction Code Byte Read Only or Read Write Object Read Write 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes Read Write R...

Page 17: ...e to download Smartlife App 4 Open APP and select Add device 5 Slide to Auto Scan 6 Press and hold on off button for 10 seconds until LCD full display Then release the button 7 APP will discover the d...

Page 18: ...r it is working normally and callibrate correctly 3 6 months 12 months 8 2 Troubleshooting procedures 8 1 Troubleshooting Introduction The purpose of this chapter is to help the operator of the unit t...

Page 19: ...C 13 14 t s 9 5 04 8 3 KT1 KT2 04 8 4 H3Y 2 C 360S 9 5 B3 KM3 A1 A2 KT2 360S H3Y 2 C 13 14 t s 9 5 04 9 3 KT2 1 T1 04 3 1 2 T2 04 3 1 3 T3 04 3 1 KM3 KT3 04 9 4 H3Y 2 C 540S 9 5 B4 KM4 A1 A2 KT3 540S...

Reviews: