background image

3

.

8

.

1

  

Drainage Pipe Test

Correctly designed condensate trap (below)

Condensate system under normal operating conditions

:

1. Level A reflects the negative static pressure.

2. Level C is at least 2 times the maximum negative static pressure.

If the unit is installed in a house before renovation, it is recommended to test before ceiling renovation

§

Please have a test after the installation of the drainage pipework.

§

During the test, determine whether the water 

ow is passing through the pipeline correctly, and carefully observe the 

§

connection to ensure that there is no water leakage at the connection

§ Avoid placing the humidity probe near heat sinks or exposed to direct sunlight, because temperature 

§

changes will affect Actual detection value.

The control circuit of the dehumidifier has been marked with different colors to prevent confusion. The 

§

unit design adopts single-phase AC power supply.

§ Before the unit is connected to the main power supply, check the single-phase AC power supply to 

§

ensure that the fluctuation range of the supplied voltage does not exceed the set point.

Prepare ±10% of marked voltage and frequency. For high load occasions (due to the conversion of larger 

§

electrical equipment) can cause voltage Volatility, this check is particularly important.

3.

10

  

 Connection of external sensitive components (control parts)

Dehumidification equipment can be pre-arranged wiring to cooperate with the external control system, 

     and provide wiring terminals for connecting external control components.

Do not install the panel where the relative humidity cannot be accurately detected, such as near a window 

§

or near a water source

The humidity detection element should be installed at a position 1 meter to 1.5 meters above the ground 

§

in order to detect representative water in the controlled area.

Flat, or laid at the inspection point according to the design requirements.

§

The unit must be grounded and a power isolation switch is provided to ensure that the equipment is cut 

§

off during inspection and service.

     comply with the following requirements:

The power supply of the dehumidification unit is equipped with a leakage protection device to make the 

§

unit safer.

The dehumidification unit cannot be operated at a voltage and frequency beyond the manufacturing 

§

range.

     When installing the humidity detection element (sensitive element), its installation position should 

11

Installed near the dehumidification equipment. The selection of the power supply cable and the main fuse 

§

should correspond to the correct operating power of the dehumidification unit.

     standards at the location of the equipment.

The fusing power of the power supply fuse must be consistent with the power and type of the installed 

§

dehumidification equipment. The fuse should be installed

3.9 

Wiring

The external control system must be compatible with the low-voltage control circuit of the dehumidification 

§

equipment.

The electrical connection must be performed by qualified personnel in accordance with the electrical

The detection element should be installed in a location that is not affected by dry or humid air and airflow 

§

outside the control area.

N

L H M L

NONC

C

fan

L

N

comp

valve

B2

A2

0-10V

C2

C1

GND

T e m p . & H u m i d i t y S e n s o r

0-10V

12V

A1

B1

A

B

+

-

-U2

12

C O N T R O L L E R

Negative pressure

Condensate pan

The fan is running

The  difference  between  A  and  C  is  at  least  the 

negative  static  pressure  of  normal  operation. 

According  to  experience,  the  difference  is  higher 

than  the  negative  static  pressure  of  normal 

operation.  Dirty  filter  or  working  fan  will  cause 

higher negative pressure.

Summary of Contents for DEH-10K

Page 1: ...g Dehumidi ers Any questions please contact the manufacturer or dealer in time The repair and maintenance must be conducted by certi fed professionals Please read the manual carefully and in full befo...

Page 2: ...ates actions that must be prohibited If not strictly followed it may cause serious damage to the machine or personal injury or death When a problem occurs such as a burning smell etc please turn off t...

Page 3: ...eck 5 2 2 Wiring Check 5 2 3 Controller Check 6 Controller 6 1 General 6 1 1 Controller Terminals 6 1 2 Terminals Diagram 6 1 3 Controller s Interface 6 1 4 Parameters Setting 6 1 5 Icon 6 2 Controlle...

Page 4: ...peration of the compressor discharge high temperature and high pressure gas from the exhaust port enter the condenser for cooling It becomes a low temperature and high pressure gas intercepted by a ca...

Page 5: ...e of the equipment can be easily carried out The unique defrosting device effectively guarantees the reliable operation of the dehumidifier The fan adopts a centrifugal external rotor fan steel volute...

Page 6: ...ane fins the heat exchange efficiency is increased by 20 thus to reduce the unit size and weight The high quality thermal insulation material increases the thermal insulation effect by 15 2 5 5 Thrott...

Page 7: ...t in humidity temp sensor I IPX3 55DB 60DB 65DB Mitsubishi R410A copper tubes with blue hydrophilic coated aluminum fins SUS304 25 32 32 G4 PRE Filter 1122 600 1850mm DEH 5K DEH 10K 11KW 22KW 20A 40A...

Page 8: ...led indoors During installation there should be maintenance space at the rear of the dehumidification equipment to facilitate future inspection and maintenance of the equipment For cleaning and mainte...

Page 9: ...alled at a position 1 meter to 1 5 meters above the ground in order to detect representative water in the controlled area Flat or laid at the inspection point according to the design requirements The...

Page 10: ...tdoors to extract air as fresh air and then sent to a separate space after dehumidification such as paint spray room purification room 4 1 2 Ducting for Fresh Air Dry air Wet air Wet fresh air Dry fre...

Page 11: ...idifier unit must be carried out by professional staff Otherwise the company will not be responsible for all the consequences caused Check the installed air filter device to ensure it is in a clean st...

Page 12: ...um fan speed Fan coil valve Low fan speed Humidifier Compressor Air damper open Air damper close EC motor supply fan EC motor exhaust fan 12VDC RS485 A1 RS485 B1 RS485 A2 RS485 B2 GND FAN 1 FAN 2 L N...

Page 13: ...umidity press to raise humidity 1 changed each press Long press Short press simultaneously for 5 seconds to display the run time wait for 5 seconds to exit Short press to set the available code Press...

Page 14: ...es later after achieved the set humidity and temperature only for the available system working mode F01 2 high fan speed low fan speed available High fan speed low fan speed available when H04 1 F01 3...

Page 15: ...rror code is E01 It will resume operation after the error addressed The error code is E03 It will resume operation after the error addressed if there is RS485 1 communication failure only the fan keep...

Page 16: ...unction Code Byte Read Only or Read Write Object Read Write 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes 2 bytes Read Write R...

Page 17: ...e to download Smartlife App 4 Open APP and select Add device 5 Slide to Auto Scan 6 Press and hold on off button for 10 seconds until LCD full display Then release the button 7 APP will discover the d...

Page 18: ...r it is working normally and callibrate correctly 3 6 months 12 months 8 2 Troubleshooting procedures 8 1 Troubleshooting Introduction The purpose of this chapter is to help the operator of the unit t...

Page 19: ...C 13 14 t s 9 5 04 8 3 KT1 KT2 04 8 4 H3Y 2 C 360S 9 5 B3 KM3 A1 A2 KT2 360S H3Y 2 C 13 14 t s 9 5 04 9 3 KT2 1 T1 04 3 1 2 T2 04 3 1 3 T3 04 3 1 KM3 KT3 04 9 4 H3Y 2 C 540S 9 5 B4 KM4 A1 A2 KT3 540S...

Reviews: