START-UP AND OPERATION
Switching the power supply of the regulator causes the regulator
to emit a sound, after which the greeting screen is displayed. After
another sound signal, the controller enters normal operation mode and
displays the first of the information screens.
NOTE! Incorrect selection of the controlled device may result in its
incorrect operation, and even in damage in extreme cases.
Quick start:
a) Select the application language in menu 2.4.
b) Set the current date and time in menu 2.3.
c) Select the controlled device in menu 2.1.
d) Set a non-zero rotation speed in menu 1.3.1.
The aforementioned procedure causes the regulated device to start
with the pre-set rotation speed.
ELECTRONIC MOTOR SPEED COTROLLER
ERO-32AP-0 V1.4
EN
2. SETTINGS
Settings of the controller.
2.1 Device type
Type selection for the controlled device (see Table 1).
2.1.1 ANeco
- Selection of a controlled device of the ANeco family.
(ANeco1-II, ANeco2-II, ANeco3-II)
2.1.2 GCKV
- Selection of a controlled device of the GCKV family.
(GCKV150, GCKV200)
2.1.3 TH/THP
- Selection of a controlled device of the TH/THP family.
(TH150T, TH150, TH200, THP200, THP250, THP300, THP350,
TH400,TH500)
2.2 Sensor type
Selection of an external sensor type.
none
- the “SENSOR” input is ignored by the controller.
analog
- the “SENSOR” input supports an analogue temperature sensor,
PT1000 type. An additional working mode (“sensor”) appears in menu
1.1, with the option to configure it in sub-menu 1.2.
digital
- the “SENSOR” input supports any sensor provided with a relay-type
(bistable) output. Additional working modes (“fixed sens.” and “fixed zone”)
appear in menu 1.1, with the option to configure them in sub-menu 1.2.
2.3 Time
Real time RTC timer settings.
2.3.1 Date
- RTC date setting.
(2000-01-01 ÷ 2099-12-31)
2.3.2 Hour
- RTC time setting.
(00:00 ÷ 23:59)
2.3.3 Time correct.
- RTC timer time setting correction.
The correction is applied each Sunday, at 00:32:40.
(-99 ÷ 99 s)
2.4 Language
Menu language selection.
(polski, english)
2.5 Display
Display parameter configuration.
2.5.1 Contrast
- Display contrast setting.
(0 ÷ 100%)
2.5.2 Backlight
- Display backlighting setting.
(0 ÷ 100%)
2.5.3 Backlight time
- Display backlighting time setting.
(1 ÷ 99 s)
2.6 Sound
Controller sound setting.
no - sound off.
yes - sound on.
2.7 Temp. Correct.
Room temperature sensor correction setting (fig. 1 item 5).
(-10 ÷ +10oC)
3. SERVICE
Service log of the controller.
3.1 Failure code
Information about malfunctions detected by the controller
(see chapter “Signalling”).
3.2 Voltages
Information about internal voltage values of the controller.
U1 (0 ÷ 6,25 V)
U2 (0 ÷ 15,3 V)
U3 (0 ÷ 27,5 V)
U4 (0 ÷ 6,250 V)
3.3 Information
Information about the controller.
(Controller name, hardware version, software version)
3.4 Reset settings
Controller reset to factory settings.
3.5 Turn off
Switches the controller off - to switch the device on again, press and hold
the knob (Fig. 1 item 3).