72
MAINTENANCE/INSPECTION CHECKLIST
(NOTE:
Maintenance/inspection items are monthly unless otherwise specified.)
Humidifier (Steam Generator) is equipped:
☐
Inspect drain valve/trap/drain line
☐
Check for leaks (makeup water/hoses)
☐
Check humidifier canister (replace if needed)
☐
Check and clean fill strainer
☐
Check operation
Record humidifier amp draw
L1
A L2
A L3
A
Reheat
☐
Inspect element (and clean if required)
☐
Check wiring
☐
Record amps
A
Refrigeration Piping
☐
Check for lines (leaks/lines secure)
☐
Check capillary lines
Condensate Pan and Pump (if equipped)
☐
Check for leaks
☐
Check for debris
☐
Inspect/check float operation
☐
Check pump operation
Condensers (Water-Cooled)
☐
Check for water/glycol leaks (in the piping area)
☐
Water regulating valve function
☐
Entering/leaving water temperatures: Entering T
°F Leaving T
°F
Compressor (Monthly):
☐
Check for oil leaks
☐
Check compressor mounting
☐
Inspect wire connection
Compressor (Quarterly)
Compressor
☐
Record suction pressure
PSIG
☐
Record discharge pressure
PSIG
☐
Record superheat
°F
☐
Record subcooling
°F
☐
Check high pressure cut-out
PSIG
☐
Check low pressure cut-in
PSIG
☐
Check low pressure cut-out
PSIG
☐
Record compressor current
L1 A L2 A L3 A