The alarm may be set to either yes or no.  Press the Enter key to move the cursor from one alarm 
to the next.  Press the Up or Down key to change from Y (yes) to N (no).

Once selections have been made and with the cursor fl ashing in the title block, press the Down 
key to see the next screen.  The following message will be displayed (entries are for reference 
only):

The alarm may be set to either yes or no.  Press the Enter key to move the cursor from one alarm 
to the next.  Press the Up or Down key to change from Y (yes) to N (no).

Once selections have been made and with the cursor fl ashing in the title block, press the Down 
key to see the next screen.  The following message will be displayed (entries are for reference 
only):

Press ESC key to get back to main menu. 

4.2 

Programming Units with Primary/Secondary Schedule

See Section 1.1.1, 

Auto Lead/Lag Standby Rotation and Temperature Assist Logic

 for details 

on unit rotation.

Once the choice of Primary/Secondary Schedule has been selected, the fi rst screen in the Set 
Zone Master Menu will display as follows (entries are for reference only):

Zone Alarm Function 4

 Stby 

Off

Override Sch 

N

Air Flow 

N

Water Flow 

N

Power-Up Y 

Y

Floor Water 

N

Hum Inhibit 

Y

Zone Alarm Function 5

 Stby 

Off

Heat Inhibit 

N

Dirty Filter 

N

Alarm SW #1 

N

Alarm SW #2 

Y

Alarm SW #3 

N

Alarm SW #4 

Y

Zone Alarm Function 6

 Stby 

Off

Manual Ovrd 

N

Hum Sensor 

N

RA Sensor 

N

Summary of Contents for dap4 touch

Page 1: ...dap4 Zone Master Supplement Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...

Page 2: ......

Page 3: ...nd Addressing Units within a Zone 9 2 0 1 Wiring 9 2 0 2 Addressing unit within a Zone 9 2 0 3 Changing the address of the dap4 controller 10 2 0 3 1 Changing the address of the Mini dap4 controller 1...

Page 4: ...on Temperature Control 1 1 Logic 1 1 1 Auto Lead Lag Standby Rotation and Temperature Assist Logic provides a means to au tomatically rotate the designation of STANDBY among a group of units that must...

Page 5: ...messages will be displayed whenever a standby unit has been reactivated for operation If the temperature and humidity condition at the standby unit are satisfied it will return to inactive STBbyZM whe...

Page 6: ...Off Day 4 ONbyZM ONbyZM STBbyZM Off Day 5 STBbyZM ONbyZM ONbyZM Off Day 6 ONbyZM STBbyZM ONbyZM Off Day 7 ONbyZM ONbyZM STBbyZM Off Note If communication with the Zone Master is broken all units will...

Page 7: ...dependent of other zones Off alarm and standby alarm selection can not be duplicated The user may assign one or more alarms as OFF by selecting Y yes in Zone Master Alarms page see programming and sel...

Page 8: ...prevented from continuing or starting humidifi cation NOTE An EXCLUDED message will display on the Zone Master when a unit is excluded from the zone by temperature or humidity calibration 1 2 Additio...

Page 9: ...lded pair with a drain line Up to 16 units may be connected in any order daisy chained Unit addresses must be assigned at start up prior to wiring Each unit is connected through the unit s control mod...

Page 10: ...Addresses needs to be done in order to establish a Zone Master communication Follow this procedure to set pLAN address to each dap4 controller in the zone Press button A for 5 seconds by using a small...

Page 11: ...hich is display __ Use UP button to change I O board address to the address that is programmed in the steps above then press Enter Display will show Terminal config press ENTER to continue press Enter...

Page 12: ...reach OK Yes No select Yes and press Enter to save the change and exit At this point the controller and the display should be communicating After addressing all individual units in a zone to the reco...

Page 13: ...r Factory Password Press the Menu button The following screen will be displayed Press the Enter key The cursor will flash on the first 0 Enter a value by pressing either the Up or Down keys Once a val...

Page 14: ...e units units 2 3 16 after they have been enabled and connected via pLAN with unit 1 master they will act as a member of the zone unless the user chooses otherwise To dis able a unit from the Zone Mas...

Page 15: ...ne and cannot be changed It shows how many units are connected to the Zone Master via the pLan connection The master unit will automatically detect the online slave units Finish Run Stdby If yes is se...

Page 16: ...ing in the title block Press the Down key The follow ing will be displayed entries are for reference only Temperature Assist Press the Enter key The cursor will flash by the current entry To change th...

Page 17: ...the standby unit the Enter key is manu ally pressed If Day Time is selected an additional line for the day time will be displayed Press the Enter key once the Day Time selection has been made The cur...

Page 18: ...in the title block press the Down key to see the next screen The follow ing message will be displayed entries are for reference only The unit may be set to either Stdby Standby or Off Press the Enter...

Page 19: ...e the next screen The following message will be displayed entries are for reference only The alarm may be set to either yes or no Press the Enter key to move the cursor from one alarm to the next Pres...

Page 20: ...ress the Down key to see the next screen The following message will be displayed entries are for reference only Press ESC key to get back to main menu 4 2 Programming Units with Primary Secondary Sche...

Page 21: ...the cursor from unit to unit Press the Up or Down key to change from Stdby to Off Once selections have been made and with the cursor flashing in the title block press the Down key to see the next scre...

Page 22: ...lock Repeat the same step for each day to be copied or select ALL Press the Enter key The cursor will flash on the No or Yes setting Pressing the Up or Down key will change from YES to NO or NO to YES...

Page 23: ...ed month and day are the STOP DATE of the holiday Press the Enter key The cursor will flash on the SETTING input Press the Up or Down keys to scroll through the choices there are two PRIMARY and SECON...

Page 24: ...been made and with the cursor flashing in the title block press the Down key to see the next screen The following message will be displayed entries are for reference only The alarm may be set to eithe...

Page 25: ...ock press the Down key to see the next screen The following message will be displayed entries are for reference only The alarm may be set to either yes or off Press the Enter key to move the cursor fr...

Page 26: ...__________________________________________________________________ __________________________________________________________________________ __________________________________________________________...

Page 27: ......

Page 28: ...dataaire com e mail sales dataaire com A Member of the CS Group of Companies 2012 Data Aire Inc Data Aire Inc reserves the right to make design changes for the purpose of product improvement or to wi...

Reviews: