62
MENU K
–
ALARMS & LIMITS (Service Level)
Alarm
Settings
Audio Mode:
None
Pwr-Up: Auto, No Alarm
Maint Due Msg:
1000hrs
Stdby Alms Active:
No
Audio Mode:
The selection for how the buzzer should sound. Selections are:
None:
Buzzer will have no sound (default setting).
Short Beep:
Buzzer will beep with an interval of 1 second on and 2
seconds off if there is an active alarm.
Long Beep:
Buzzer will beep with an interval of 3 seconds on and 2
seconds off if there is an active alarm.
Full On:
Buzzer will be constantly on as long as there is an active alarm.
Power-Up
: Selection of what the controller should do when power is restored.
Auto. No Alarm:
(Default selection) There will be no alarm and startup as
normal.
Auto. With Alm:
There will be an alarm and startup as normal.
Man. Clr Alarm:
There will be an alarm and controller will not startup until
the alarm is acknowledged.
Maint Due Message:
The message due alarm can be disabled by setting it to
“None” (the default) otherwise, the alarm will occur in the time selected. The range
of time is 1 to 1000 hours. The maintenance due alarm can be cleared by
acknowledging the alarm and then pressing the Alarm key again.
Stdby Alms Active:
Allows some general alarm switches and conditions to remain
active (like when unit is on) in the Standby Mode or when standby from Zone
Control. Instead of the normal Off by BMS mode, the unit will be put in standby.
This feature helps to determine if the unit is suitable to operate. The default setting
for this alarm option is No.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...