72
MENU K
– ALARMS & LIMITS (Service Level) continued
CO2 Alarms
Low CO2 Alarm:
Yes
Setpoint:
100ppm
High CO2 Alarm:
Yes
Setpoint: 2000ppm
This CO2 Alarms screen is only shown on the gPOD model.
CO2 alarms are warnings only and will not prevent any of the unit functions from
operating.
Low CO2 Alarm:
When set to
“Yes” (default setting), the alarm is enabled.
Set Point:
This is the lowest CO2 level that will cause an alarm. Range of
adjustment is 100 to 5000ppm with a default setting of 100ppm.
High CO2 Alarm:
When set to
“Yes” (default setting), the alarm is enabled.
Set Point:
This is the highest CO2 level that will cause an alarm. Range of
adjustment is 100 to 5000ppm with a default setting of 2000ppm.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...