Data Industrial Series 340 Btu transmitter Owner’s Manual

4

Temp
2

Temp
1

Mat

10K Thermistors

NOTE:
maximum sinking current 
is 100 mA @ 36 VDC.  

Pulse Input

Device

(-)

(+)

Po

w

er I

AC L/DC 

+

AC C/DC

Ou
tp

ut

Pulse Out

-

Pulse Out

+

Output LED

Temperature Element Wiring

The Data Industrial thermistors are not polarity sensitive.
Connect thermistor closest to the flow sensor to Series 340
terminal block marked TEMP 1 and the other thermistor
wires to Series 340 terminal marked TEMP 2.

Pulse Output Wiring

The Series 340 has solid state switch output rated for a
maximum sinking current of 100 mA @ 36 VDC. In most
cases the pulse out (+) terminal of the 340 will connect to
the Input pulse (+) and the pulse out (-) terminal to the Input
pulse (-) of the receiving device. These terminals are located
on a separate two terminal removable header on the 340
labeled “Output”. Observe the electrical polarity of the
output.

Communications cable wiring

Field calibration requires a Data Industrial A340 Programming kit (consisting of a custom cable and
software) and a PC running Windows

®

 9x, ME, NT or 2000.  In order to calibrate, the Series 340 must

be connected to power, and the A301 cable must be connected to the 340 Comm port connector and an
available 9-pin COM port on a computer.

Note:
The Data Industrial A301 Cable will work
with all 300 Series products. However
the older version of the cable (A300)
does not have sufficient bandwidth to
work with the Series 340 Transmitters.

Data Industrial provides free programming
software updates via the Internet for all of
Series 300 devices. Go to
www.dataindustrial.com for these updates.

Sample Pulse Output wiring

Diagram

Thermistor Wiring Diagram

Location of the

DIC Communication Port

DIC Comm Port

(Plug in A301 Program Cable here to program)

Se

ns

or

 In

Power Out
Signal 

+

Signal

-

Po

w

er I

n

AC L/DC 

+

AC C/DC

-

Ou
tp

ut

Pulse Out

-

Pulse Out

+

Output LED

Model: 340

Input LED

D.

I.C

.

Co
m

m

Po

rt

Summary of Contents for 340 Series

Page 1: ...puter real time flow rate flow total both temperature readings energy rate and energy total are available The Series 340 transmitter features two LED s to verify input and output signals The standard output for the Series 340 is an isolated solid state switch closure that is user programmed for units of energy or flow The output pulse width is adjustable from 50 mS to 5 sec The Series 340 Btu tran...

Page 2: ...ment of the programming cable The unit generates very little heat so no consideration need be given to cooling or ventilation Surface Mount Installation The 340 may be mounted to the surface of any panel using double sided adhesive tape or by attaching fasteners through the holes in the mounting flanges of the unit Din rail Mounting Optional clips snap onto the mounting flanges allowing the 340 to...

Page 3: ...is used connect the black white striped wire to the terminal marked positive and the black wire to the terminal marked negative Note Included with every Series 340 is a 340IK kit containing a screw lock washer and nut to connect the Series 340 to Earth Ground Connect the Earth Ground Lug of the Series 340 to a solid Earth Ground with as short a wire as possible This will help prevent electrical in...

Page 4: ...rve the electrical polarity of the output Communications cable wiring Field calibration requires a Data Industrial A340 Programming kit consisting of a custom cable and software and a PC running Windows 9x ME NT or 2000 In order to calibrate the Series 340 must be connected to power and the A301 cable must be connected to the 340 Comm port connector and an available 9 pin COM port on a computer No...

Page 5: ...ustrial A 301 communications cable to the socket labeled D I C Comm Port taking care to properly align the tab on the plug and socket to maintain polarity Connect the DB9 connector of the Data Industrial A301 communications cable to a PC com port that has the 340 software installed 3 Connect the Series 340 transmitter to a power supply 4 Open the interface software and select the appropriate COM P...

Page 6: ...ed with 10 providing the greatest degree of smoothing See the Dialog Box below 6 Program using diagram below as a reference Step 1 see note 1 Select the flow sensor type sine or pulse and enter the k and offset Step 4 Select the desired flow rate and total units here Step 7 Press send to transmit calibration data to the 340 Step 5 Select the desired energy rate and total units here Step 2 Select t...

Page 7: ...ce Opto isolated solid state switch Operating Voltage range 0 60V DC or AC peak Closed on state Load Current 700mA max over operating temperature range On resistance 700mΩ max over operating temperature range Open off state leakage 70 C 1 A 60V DC or AC peak Operating Temperature 29 C to 70 C 20 F to 158 F Storage Temperature 40 C to 85 C 40 F to 185 F Weight 4 8 oz With headers installed SENSOR C...

Page 8: ... a Version n a Temperature Units F Sensor Type Pulse K 1 offset 0 Flow Rate Units gpm Flow Total Units gallons Energy Rate Units kBtu hr Energy Total Units Btu Energy Calculation absolute Flow Filter 0 Energy Filter 0 Scaled Pulse Output Units energy Scaled Pulse Output Units Per Pulse 1 Scaled Pulse Output Pulse Width 100 ...

Page 9: ...ress Seller may at its sole option instruct Buyer to ship subject part postage prepaid to the Seller at above address or authorize a representative to inspect the part on site Seller will at its sole option repair or replace any defective product covered by this warranty If Buyer makes repairs or alterations to any product or part covered by this warranty without Sellers prior written approval thi...