Voltage & Current Inputs

Ranges

±100mV, ±10V DC and ±20mA DC.

Input Impedance (Ohms)

>500M

, >1M

 and <5

.

Sensor Excitation Supply (Tracker 321 and 332 only)

2-wire loop supply

24V DC nominally @ 35mA max.

Bridge supply

10V DC regulated @ 35mA max.

Isolation

functional isolation only.

Thermocouple Measurement

Resistance Thermometers

Configuration

2 or 3 wire.

Communications Interface

Isolation

500V DC/peak AC.

Type

RS485 2-wire multidrop.

Protocols

MODBUS RTU & ASCII, DTPI (ASCII)

Analogue Output

Isolation

500V DC/peak AC.

Output

Selectable 0 to 10V, 0 to 20mA or 4 to 20mA.

Maximum current output

22mA @ 18V.

Maximum voltage output

11V @ 22mA.

Maximum load (mA output) 900 Ohms.

Logic Outputs (Tracker 331 only)

Relay type

1 x normally open contacts. (Optionally 2.)

Rating

1A @ 230V AC, 1A @ 30V DC.

Relay isolation

Isolated from each other and all other inputs 

and outputs.

SSR drive output

18V DC 20mA nominal
(see also Tracker 340 Logic Module).

Partial Load Failure Feedback

4 to 20mA or 0 to 10V DC input from an external current transmitter. The 
CT signal must be a different signal type from the PV signal.

Packing List

The following items are included in the package with the instrument.

Mini CD (80 mm diameter) The CD contains the Reference Manual in PDF 

format, foreign language Installation Guides 
in PDF format, the instrument configuration 
software and additional freeware utilities.

Installation Guide

Folded A3 Installation Guide detailing safety 

and connection information.

Tracker 340 Expansion Module

1.  Introduction

The Tracker 340 expansion module is connected to a Tracker 300 series 
instrument via the expansion port.  The Tracker 340 is powered by and 
configured via the Tracker 300.

2.  Connections

The diagram below shows the terminal connection arrangement. 

Relay Connections

Logic Connections

3.  Connecting the Status Inputs

There are two status (logic) inputs provided on the Tracker 340 expansion 
module. The inputs can be used with either voltage free contacts, such as 
relay contacts, switches, open collector transitor outputs, or voltage driven. 
The inputs are active low, i.e. apply a short circuit between the status input 
and status common. The following diagrams illustrate typical applications. 

Status Input 1

Status Input 2

Voltage Free
Contacts

Open Collector
TTL Outputs

Voltage Driven

Note: 0V is active

4.  Indicators

There are six LEDs on the front panel of the instrument, two green (input) 
and four red (output). 

Green LED Status Inputs 1 & 2– lit when the respective status input is 
active.
Red LED 1, 2, 3 and 4

– programmable LEDs.

5.  Specification

Relay Option

Relays

4 off, change over

Rating

1A @ 230V AC, 1A @ 30V DC

Relay isolation

Isolated from each other and all other inputs 
and outputs

TTL Logic Option

Drivers

4 off, TTL

Rating

±20mA, source or sink

Isolation

No isolation

Status Inputs (both options)

Logic inputs

2 off, voltage free or TTL

Protection

Reverse diode protected

D

ATA 

T

RACK 

Process Instruments Ltd

153 Somerford Road

Christchurch, Dorset BH23 3TY

United Kingdom

TRACKER 300 SERIES

INSTALLATION GUIDE

DATA TRACK
PROCESS INSTRUMENTS

Accuracy Including Linearisation

Thermocouple

Range (

o

C) Worst Case

Typical @ 20°C

Type B, Pt30%Rh/Pt6%Rh

0 to 1820

±1.0°C

±0.5°C

Type J, Fe/NiCu

-210 to 1200

±1.0°C

±0.5°C

Type K, NiCh/Ni/Al

-270 to 1372

±1.0°C

±0.5°C

Type T, Cu/CuNi

-270 to 400

±1.0°C

±0.5°C

Type N, Nicrosil-Nisil

-200 to 1300

±1.0°C

±0.5°C

Type R, Pt13%Rh-Pt

-50 to 1767

±2.0°C

±1.2°C

Type S, Pt10%Rh-Pt

-50 to 1767

±2.0°C

±1.2°C

Accuracy Including Linearisation

RTD Type

Range (

o

C)

Worst Case

Typical @ 20°C

Pt100 (alpha = 385)

-200 to 850

±0.8°C

±0.4°C

Pt100 (alpha = 392)

-270 to 457

±0.8°C

±0.4°C

1

2

3

4

5

7

6

8

9

10

11

12

13

15

14

16

C
NO
NC

NC
NO
C

NC
NO
C

C
NO
NC

Relay1

Relay2

Relay3

Relay4

C - Common

NO - Normally Open
NC - Normally Closed

0V
O/P

Logic1

Logic2

Logic3

Logic4

O/P
0V

O/P
0V

0V
O/P

0V

0V

5V

0V

0V

5V