background image

 

 

During auto setup : 

- Polarity and unmatched current 
transformers connection will be corrected.   

Each step’s reactive power and 

connection type will be automatically 
measured. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUTTON 

FUNCTION 

 

Hold pressed MENU button for 3 
seconds to activate auto setup. 

LErn

 should be seen at top 

screen.  

 

Push up arrow buttons 4 times to 
navigate 

ctrF 

parameter.  

This parameter refers to primary 
value of current transformer. 
Secondary value is configured as 
5A and can not be changed.   

 

Click

 MENU

 button to see the 

ctrF

 

parameter. This is the primary 
value of current transformer. 500A 
is configured as default. 

 

Adjust primary value of current 
transformer by using up and down 
arrow buttons. If current 
transformer is 150/5A, 

ctrF

 should 

be adjusted to 150. 

 

Click

 MENU

 button to save 

ctrF

 

(adjusted value will disappear)  

 

Click arrow down button 4 times to 
display the 

LErn

 parameter.  

 

Click 

MENU

 button once more to 

see value of 

LErn

 parameter. (Will 

be 0 as default) 

 

Adjust value of

 LErn 

to

 

1 by 

clicking up arrow button. 

 Auto setup (3+2) 

 Step values learning 

 CT connection correction 

 

Click 

MENU

 button to enable auto 

setup. Device will check and 
correct current transformer 
connections. After that, reactive 
power of each step will be 
measured by the auto learning 
function. 
After successful auto setup, AUTO 
led will turn on, and steps will be 
swithced on and off depending on 
the reactive power demand of the 
load. 

 

 

 

 

 

 

 

2. AUTO SETUP 

 

 

Three phase voltage 
inputs must be 
connected for successful 
auto setup.  

 

 

Large size three phase 
capacitors or reactors 
should be connected to 
first steps for successful 
auto setup.  

 

 

 

Disconnecting the installation side is 
preferred during auto setup. However, 
the device can manage to complete 
auto setup with stable installation load. 
Fast varying loads might cause 
inaccurate detection of reactive power 
as well as faulty current transformer 
polarity. 
In such cases, auto setup should be 
repeated and connected capacitors 
and/or inductors should be checked. 
 

 

Summary of Contents for DFC-0115

Page 1: ...e unit Verify correct terminal connections before applying power Only for front panel mounting Before Installation Read the user manual carefully determine the correct connection diagram Remove all connectors and mounting brackets from the unit then pass the unit through the mounting opening Put mounting brackets and tighten Do not tighten too much this can break the enclosure Make electrical conn...

Page 2: ...roportionally Current transformers must have a 5A output Three buttons on the front panel provide access to configuration and measurement screens BUTTON FUNCTION Remove all alarms in AUTO mode If the same alarm occurs again it will not be displayed When held pressed for 3 seconds Programming mode activated All alarms are enabled Skip to the next parameter Measurement and parameter screen Increase ...

Page 3: ...nce more to see value of LErn parameter Will be 0 as default Adjust value of LErn to 1 by clicking up arrow button 1 Auto setup 3 2 2 Step values learning 3 CT connection correction Click MENU button to enable auto setup Device will check and correct current transformer connections After that reactive power of each step will be measured by the auto learning function After successful auto setup AUT...

Page 4: ...n is held pressed When the required password is set click MENU button First parameter should be seen LErn if correct password is typed Hold down MENU button for 3 seconds and LAMP TEST mode will be activated All LEDs on the device will turn on Click MENU button again to navigate through measurement screens BUTTON FUNCTION Choose required parameter by using up and down arrows while parameter can be...

Page 5: ... 1 FCty Return to factory settings When this parameter is set to 1 all parameters will return to their factory set values 0 0 1 DEFINITION MIN STD MAX CtrF Current Transformer Primary value of current transformers Can be set between 5 5A and 5000 5A 5A 500A 5000A CoS Target Cosø Target Cosø can be set between capacitive 0 800 and inductive 0 800 Capacitive power factor is displayed as c 800 while ...

Page 6: ...calculated at the end of this delay 1 sec 1 sec 2000 sec t CL Step switching protection delay When the unit sets a new step configuration all step switching will be disabled during this timer 0 sec 1 sec 2000 sec dCHr Discharge timer This is the common discharge timer for all steps Any step swithed off cannot be switched on again before expiration of this timer 3 sec 14 sec 2000 sec ...

Page 7: ...se Current Inputs 0 5VA per phase Number of Steps 12 15 Relay Outputs 5A 250V A Serial Port Signal Type RS 485 Communication Modbus RTU Baud Rate 2400 115200 selectable Isolation 500V AC 1 minute Operating Temperature 20 C to 70 C 4 to 158 F Maximum Humidity 95 non condensing Degree of Protection IP 54 Front Panel IP 30 Rear Panell Enclosure Non flammable ROHS compliant Flame retardant High temp A...

Page 8: ...Tel 90 216 466 84 60 Fax 90 216 364 65 65 e mail datakom datakom com tr http www datakom com tr CONNECTION DIAGRAM ...

Reviews: