5.7.9.2. Relays and digital inputs for controlling the BDS (Type 2)
The relays associated to arming or disarming the alarm sections are set
up according the entries described in this chapter. Additionally the digi-
tal input to indicate the readiness to be armed and the armed-state of
the BDS section is configured here.
Beschreibung ReaderProbs für (Type=2) Ein- und Ausgänge Definition!
Please note:
-
If arming and disarming is using the same relay, the values in columns OutUnarm-
Reader and OutUnarmPort have to be identical to OutArmReader and
OutArmPort. If the relay then is closed, the BDS is meant to be armed, the opened
relay indicates the disarmed BDS.
-
If no digital input is set as „InRdyRead“, the BDS is considered to be ready to be
armed any time.
Column
Name
I the Setup
Data
type
Length
Description
1
RefReader
Number
(int)
4
Not required, leave empty
2
Type
Number
(int)
variable
10
Type 2 = BDS
–
definition entry for relay and digital input
3
Area
Number
(int)
variabel
max. 10
Number associated to the BDS
section
4
OutArmReader
Number
(int)
4
Reference to the device (controller or bus member) that contains the
relay
for
arming
the BDS.
5
OutArmPort
1-
9; A…
1
Nummer den Ausgangs
6
OutUnarmReader
Number
(int)
4
Reference to the device (controller or bus member) that contains the
relay
for
disarming
the BDS.
7
OutUnarmPort
1-
9; A…
1
Number of the relay on the device column 6
8
InRdyReader
Number
(int)
4
Reference to the device (controller or bus member) that contains the
digital
input
that signals the BDS section to be
ready to be armed
(through “high”
voltage level).
9
InRdyPort
1-
9; A…
1
Number of the relay on the device column 8
10
InArmedReader
Number
(int)
4
Reference to the device (controller or bus member) that contains the
digital
input signallin
g that
the BDS section is armed
(through “high” voltage level).
11
InArmedPort
1-
9; A…
1
Number of the relay on the device column 8
12
OutElapse
Number
(int)
4
0 -> The relay for arming / disarming is continuous active, otherwise duration
of the relay’s closing time in seconds.