Manual Datafox KYO Inloc
page 79
date: 16.12.2020 Version: 04.03.15.XX
Correct!
Correct bus wiring of the access readers with star-shaped cable routing.
The wiring must not be parallel from one point. The wire pairs A and B must each be routed in se-
ries directly to the terminal of a reader and from there on to the next bus device in order to ensure
smooth operation of the bus communication.
RS485 A-B AC Master
e.g.: Datafox KYO Inloc
External power supply
Datafox EVO Intera 1
Datafox EVO Intera 2
Datafox EVO Intera 3
RS 485 twisted pair
of wires
yellow/white
RS 485 twisted pair
of wires
green/white
Junction box
+12V
GND
A cable can be led to the reader, ex-
ample: Cat cable,
Telecommunications cable
(JY(ST)Y), or similar