DKG-119J User Manual V-32
(09.07.2012)
- 31 -
The program mode is used to program timers, operational limits and the configuration of the unit.
To
enter the program mode
, press together
◄
MENU
and
MENU
►
buttons for 1 second.
The program mode is only allowed if the
PROGRAM LOCK
input is left open. If this input is tied to
GROUND
, the program value modification will be disabled to prevent unauthorized intervention. It is
advised to keep the
PROGRAM LOCK
input tied to
GROUND
.
When the program mode is entered, below password entry screen will be displayed.
A 4 digit password must be entered using
▼,
▲
, MENU
►
and
◄
MENU
buttons.
The unit stores 3 different passwords. Each password allows access to a different level of
program parameters.
The password level-1 allows access to field adjusted parameters. The level-2 allows access to
factory setup. The password level-3 is reserved to Datakom and allows access to calibration
parameters.
Passwords can only be modified through Rainbow program.
The program mode will not affect the operation of the unit. Thus programs may be modified
anytime, even while the genset is running.
The program mode is driven with a two level menu system. The top menu consists on program
groups and each group consists of various program parameters.
When program mode is entered, a list of available groups will be displayed. Navigation
between different groups are made with
▼
and
▲
buttons. Selected group is shown in reverse video
(blue on white). In order to enter inside a group, please press
MENU
►
button. In order to exit from the
group to the main list please press
◄
MENU
button.
Navigation inside a group is made also with
▼
and
▲
buttons. A list of available parameters
will be displayed. Selected parameter is shown in reverse video (blue on white). In order
display/change the value of this parameter, please press
MENU
►
button. Parameter value may be
increased and decreased with
▼
and
▲
buttons. If these keys are hold pressed, the program value will
be increased/decreased by steps of 10. When a program parameter is modified, it is automatically
saved in memory. If
MENU
►
button is pressed, next parameter will be displayed. If
◄
MENU
button is
pressed, then the list of parameters in this group will be displayed.
Program parameters are kept in a non-volatile memory and are not affected from power
failures.
To
exit the program mode
press one of the mode selection keys. If no button is pressed
during 1 minute the program mode will be cancelled automatically.
The password level-
1 is factory set to „1234‟.
The password level-
2 is factory set to „9876‟.
A logic level to RS-232 converter is necessary
in order to connect the unit to modem.
12. PROGRAMMING