DKG-119J User Manual V-32
(09.07.2012)
- 42 -
Program Group: Input Configuration (Emergency Stop)
(password level-2)
Parameter Definition
Unit
Fac.Set Description
Action
0
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
Latching
0
0:
Non latching
1:
Latching
Contact type
0
0:
Normally open
1:
Normally closed
Switching
0
0:
Battery negative
1:
Battery positive
Response delay
0
0:
No delay
1:
Delayed (4sec)
Program Group: Input Configuration (Spare
–1 Input)
(password level-2)
Parameter Definition
Unit
Fac.Set Description
Action
2
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
Latching
0
0:
Non latching
1:
Latching
Contact type
0
0:
Normally open
1:
Normally closed
Switching
0
0:
Battery negative
1:
Battery positive
Response delay
0
0:
No delay
1:
Delayed (4sec)