DKM-260 User Manual V-1.0
18
The firmware version is displayed in te second line of the “
end
end
end
end
,
End”
screen.
Any inquiry to the manufacturer must state the firmware version in
question.
The unit leaves the production in a calibrated status.
If recalibration is required, enter the password “3282” to the third line
of the “
end
end
end
end
,
End” screen and press the SET button.
The calibration screen about the 110V voltage input will be seen. The
first display will show “110V”. The second screen will display the
measured instantaneous voltage from the input. The third display will
display the calibration coefficient (high 4 digits only)
Adjust UP and DOWN menu buttons until the value displayed in the
second screen is correct.
When the value is correct then press SET button. The unit will switch
to first current input sensitivity calibration.
4.12 DISPLAYING THE FIRMWARE VERSION
4.13 CALIBRATION