Although the unit is protected against 
electromagnetic disturbance, excessive disturbance 
can affect the operation, measurement precision and 
data communication quality. 

 

Use cables of appropriate temperature range. 

 

Use adequate cable section, at least 0.75mm

(AWG18).  

 

For current transformer inputs, use at least 
1.5mm

2

 section (AWG15) cable. 

 

The current transformer cable length should 
not exceed 1.5 meters. If longer cable is used, 
increase the cable section proportionally. 

 

Current transformers must have 5A output. 

 

 

 

 

 

 

 

 

 

 

Power Supply Input:

  

     170 - 275VAC, 45 

– 66 Hz  

     Different AC supply voltages available. 

Measurement Input Range:  
     Voltage inputs: 
 

10 - 300 V AC (L-N) 

 

20 - 520 V AC (L-L) 

     Current inputs: 

0.2 

– 5.5 A AC 

     Frequency: 

30 - 100 Hz

  

Accuracy:

  

 

 

     Voltage: 

 

0.5%+1digit 

     Current: 

 

0.5%+1 digit 

     Frequency: 

0.5%+1 digit 

Measurement Range: 

 

     CT range:   

5

/

5A to 5000

/

5A  

Power Consumption:

  

< 4 W 

Voltage burden: 

< 0.1VA per phase  

Current burden: 

< 1VA per phase 

 

 
Operating Temperature: 
 

-

20°C to +80°C (-4 to +176 

F). 

Maximum humidity:

  

 

95% non-condensing.

 

Degree of Protection: 
 

 IP 54 (Front Panel) , 

 

 IP 30 (Back panel)

 

Enclosure:

    

 

Non-flammable, ROHS compliant, 
ABS/PC (UL94-V0)

 

Installation: 

Flush mounting with rear retaining 
brackets

 

Dimensions: 
 

102x102x53mm (WxHxD) 

Panel Cutout: 

92x92mm 

 

Weight:

            200 gr 

 

TECHNICAL SPECIFICATIONS 

 

REQUIRED PANEL DEPTH 

 

PANEL CUTOUT 

 

 

Current Transformers must be 
used for current measurement.  

No direct connection allowed 

 

 

Do not install the unit close 
to high electromagnetic 
noise emitting devices like 
contactors, high current 
busbars, switchmode power 
supplies and the like.

 

 

ELECTRICAL INSTALLATION 

 