Parameter value:
0:
No action
1:
Reset alarms
Setting this parameter to 1 will reset
existing alarms.
The parameter value is not stored into
memory and reads always 0.
This parameter selects the default screen
that the unit returns 5 minutes after any
key is pressed.
Setting this parameter to 0 will cancel the
default screen.
Param.
değeri
Göstergeler
0
no change
1
Voltages L-N
2
Voltages L-L
3
Currents
4
Total current
5
Phase kW
6
Total kW
7
Phase kVAr
8
Total kVAr
9
Phase kVA
10
Total kVA
11
Phase
cosø
12
Total
cosø
13
Frequency
14
kWh counter
15
kVArh counter
16
Hours counter
4.6 SETTING THE DEFAULT SCREEN
4.5 RESETTING ALARMS