This parameter sets the high limit for high
voltage alarm.
Only
phase to neutral
voltages are
monitored and generate alarms.
If the parameter is set to 0 then no high
voltage alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 12’000volts
This parameter sets the low limit for low
voltage alarm.
Only
phase to neutral
voltages are
monitored and generate alarms.
If the parameter is set to 0 then no low
voltage alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 12’000volts
4.9 SETTING HIGH AND LOW VOLTAGE LIMITS